STEP 3 -- INSTALLING INDOOR EXPANSION VALVE

This outdoor unit is designed for use in systems that include an check/expansion valve metering device. See the SPB*H4
Product Specifications bulletin (EHB) for approved check/expansion valve kit match-ups and application information. The
check/expansion valve can be installed internal or external to the indoor coil. In applications where an uncased coil is being
installed in a field-provided plenum, install the check/expansion valve in a manner that will provide access for future field
service of the check/expansion valve. Refer to below illustration for reference during installation of check/expansion valve.
TWO PIECE
(Uncased Coil Shown)
PATCH PLATE
(UNCASED
LIQUID LINE
COIL ONLY)
ORIFICE
HOUSING
DISTRIBUTOR
TUBES
DISTRIBUTOR
ASSEMBLY
MALE EQUALIZER LINE
FITTING
(SEE EQUALIZER LINE
INSTALLATION FOR
FURTHER DETAILS)
Sensing bulb insulation is required if mounted
external to the coil casing. See Sensing Bulb
Installation for bulb positioning.
EQUALIZER LINE INSTALLATION
1.
Remove and discard either the flare seal cap or flare nut
with copper flare seal bonnet from the equalizer line port on
the vapor line as illustrated in the figure below.
2.
Remove the field-provided fitting that temporarily recon­
nected the liquid line to the indoor unit's distributor assembly.
FLARE SEAL CAP
INDOOR EXPANSION VALVE INSTALLATION
STUB
CHECK
END
EXPANSION
VALVE
TEFLON
RING
®
TEFLON
SENSING
RING
EQUALIZER
LINE
LIQUID LINE
ASSEMBLY WITH
BRASS NUT
VAPOR
LINE
LIQUID LINE
FLARE NUT
COPPER FLARE
OR
SEAL BONNET
MALE BRASS EQUALIZER
LINE FITTING
VAPOR LINE
3.
Install one of the provided Teflon
stubbed end of the check expansion valve and lightly
lubricate the connector threads and expose surface of
®
the Teflon
ring with refrigerant oil.
4.
Attach the stubbed end of the check expansion valve to
the liquid line orifice housing. Finger tighten and use an
®
appropriately sized wrench to turn an additional 1/2 turn
clockwise as illustrated in the figure above, or tighten to
20 ft-lb.
5.
Place the remaining Teflon
end of the check expansion valve. Lightly lubricate
connector threads and expose surface of the Teflon
LINE
ring with refrigerant oil.
6.
Attach the liquid line assembly to the check expansion
valve. Finger tighten and use an appropriately sized
wrench to turn an additional 1/2 turn clockwise as
illustrated in the figure above or tighten to 20 ft-lb.
SENSING BULB INSTALLATION
1.
Attach the vapor line sensing bulb in the proper
orientation, as illustrated below, using the clamp and
screws provided.
NOTE - Confirm proper thermal contact between vapor
line and sensing bulb before insulating the sensing bulb
once installed.
2.
Connect the equalizer line from the check/expansion
valve to the equalizer vapor port on the vapor line. Finger
tighten the flare nut plus 1/8 turn (7 ft-lbs) as illustrated
below.
9 O'CLOCK TO
BULB
VAPOR LINE
VAPOR LINE
BULB
NOTE - NEVER MOUNT THE SENSING BULB ON
FIGURE 8
Page 8
®
rings around the
®
washer around the other
3 O'CLOCK
ON LINES SMALLER THAN
7/8",
12
BULB
BULB BETWEEN THE 9 AND
3 O'CLOCK POSITIONS.
ON 7/8" AND LARGER LINES,
MOUNT SENSING BULB AT
EITHER THE 4 OR 8 O'CLOCK
POSITION.
THE
12
BOTTOM OF LINE.
BULB
BOTTOM OF LINE.
1/2 Turn
11 12
1
2
10
9
3
4
8
5
7
6
®
1/8 Turn
11 12
1
2
10
9
3
4
8
5
7
6
MOUNT
SENSING
NEVER
MOUNT
SENSING
BULB
ON

Advertisement