4.10.3 Gas Train Installation - Riello 40 FSP20 Installation, Use And Maintenance Instructions

Forced draught gas burner
Table of Contents

Advertisement

4.10.3 Gas train installation

Disconnect the electrical power using the main
switch.
DANGER
Check that there are no gas leaks.
Pay attention when handling the train: danger of
crushing of limbs.
Make sure that the gas train is properly installed
by checking for any fuel leaks.
The gas train 1)(Fig. 15) can be installed on both the left side and
the right side of the burner.
Connection between the gas supply line and the train must be
made using the gas-in flange 3) supplied, and fastening screws.
It is best to tighten screws in a criss-cross pattern.
Do not, under any circumstances, install the valve
with the coil facing down.
WARNING
To carry out the electrical wiring to the terminal board of the burn-
er:
 unscrew the screws of the 6 pin plug 2)(Fig. 15) of the gas
train;
 connect the flying leads as shown in "Standard wiring dia-
gram" on page 19.
Once installation is complete, you must check for
fuel leaks and make sure the gas train is working
properly.
WARNING
20064802
Installation
16
GB
20065572
Fig. 15