Mitsubishi Electric Mr.Slim PCA-M35KA2 Service Manual page 59

Split-type, heat pump air conditioners split-type, air conditioners ceiling suspended r32/r410a
Table of Contents

Advertisement

13-6. ROTATION SETTING
Setting method of each function by wired remote controller
■ PAR-41MAA
Stop operation
1.
Select "Service" from the Main menu, and press the [
Select "Settings" with the F1 or F2 button, and press the [
Select "Rotation setting" with the F1 or F2 button, and press the [
2. Set the rotation function.
Select "Rotation" with the F1 button.
Select the rotation period or "Backup only" with the F2 or F3 button.
■ "Rotation" setup
None, 1 day, 3 days, 5 days, 7 days, 14 days, 28days, Backup only
Notes:
When 1 to 28 days are selected, the backup function is also enabled.
When "Backup only" is selected, the rotation function will be disabled. The sys-
tems with refrigerant addresses of 00 or 01 (00 system/ 01 system) will be oper-
ated as a main system while the 02 system is the standby mode as backup.
3. Set the support function.
Select "TempDifTrigger" with the F1 button.
Select "the difference between the suction temperature and the set temperature"
with the F2 or F3 button.
■ "TempDifTrigger" setup
None, +4ºC, +6ºC, +8ºC
Notes:
The support function is available only in the COOL mode. (Not available in the
HEAT, DRY and AUTO mode.)
The support function is enabled when any option other than "None" is selected
from the "Rotation" setup.
4. Update the setting.
Press the [
] button to update the setting.
Reset method
Press the F4 button in step 2 or 3 to reset the operation time of the rotation function. Once it is reset, operation will
start from the 00 or 01 systems.
Note: When the 02 system is in the backup operation, the 00 or 01 systems will be operated again.
OCH752
] button.
] button.
] button.
59
Settings menu
Function setting
Rotation setting
Service menu:
Cursor
F1
F2
F3
F4
Rotation setting
Rotation
Backup only
TempDifTrigger
+4°C
Select :
Cur.
− Content +
R
e
F1
F2
F3
F4
Rotation setting
Rotation
Backup only
+4°C
TempDifTrigger
Select :
Cur.
− Content +
R
e
F1
F2
F3
F4
s
t e
s
t e

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mr.slim pca seriesMr.slim pca-m35ka2-etMr.slim pca-m35ka2-erMr.slim pca-m50ka2Mr.slim pca-m50ka2-etMr.slim pca-m50ka2-er ... Show all