OPERATING PROCEDURE
10. Removing the pipe temperature thermistors/liquid (TH2)
and condenser/evaporator temperature thermistor (TH5)
(1) Remove the air intake grille. (See Figure 1, 2)
(2) Remove the left and right side panels. (See Figure 3,4)
(3) Remove the under panel. (See Photo 14)
(4) Remove the drain pan. (See Photo 15, 16, 17)
(5) Disconnect the connector CN44 (white) from the indoor
controller board.
(6) Remove 6 screws from the pipe cover and remove the
pipe cover. (See Photo 15, 18)
(7) Remove the fastener for wires and remove the thermistors
(TH2 and TH5) from each holder. (See Photo 19)
11. Removing the guide vane
(1) Remove the intake grille. (See Figure 1, 2)
(2) Remove the side panel (right and left). (See Figure 3, 4)
(3) Remove the under panel. (See Photo 14)
(4) Remove the drain pan. (See Photo 15,16,17)
(5) Remove the screw from the guide vane, then remove
the guide vane.
12. Removing the Auto vane
(1) Remove the intake grille. (See Figure 1, 2)
(2) Remove the right side panel. (See Figure 3, 4)
(3) Remove the vane motor and cover. (See Photo 13)
(4) Slide the auto vane to the vane motor side.
(5) Remove 2 axes from each vane support pushing the
vane support to the vane sleeve side.
OCH752
PHOTOS/FIGURES
Photo 18
Pipe cover fixing
screws
Pipe cover
Photo 19
Condenser/evaporator
temperature thermistor
(TH5)
Pipe tempera-
ture thermistor/
liquid (TH2)
Photo 20
Screw
Guide vane
Photo 21
Vane sleeve
40
Pipe cover fix-
ing screws
(See Photo 15)
Fastener
Drain pan
Vane support
Vane
Vane motor side