Daytime/Nighttime Sensitivity; Holiday Days - Honeywell Farenhyt IFP-2000 Manual

Analog/ addressable fire system, emergency communication system
Table of Contents

Advertisement

Model IFP-2000/ECS Installation Manual
9.6.3

Daytime/Nighttime Sensitivity

If you need to change the time that sensitivity levels take effect (that is, the time that "Day" and "Night" begin),
follow these steps.
1.
Enter the installer code. The panel will automatically go to the main menu.
1.
Select 7 for Panel Programming.
2.
Select 5 for System Options.
3.
From System Options, select 2 for Daytime/Nighttime Sensitivity.
A screen similar to the one shown in Figure 9-11 will display.
9.6.4

Holiday Days

Up to 18 dates can be designated as holidays. When day/night sensitivity is enabled, all photoelectric smoke
detectors in the system will use night sensitivity for the entire day on days designated as holidays.
To add or change a holiday, follow these steps:
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
3.
Select 5 for System Options.
4.
Select 3 for Holiday Days. A screen similar to that shown in Figure 9-12 will display.
5.
Edit the holiday schedules you wish to change or add holidays as needed in the programmable holiday loca-
tions.
Pre-programed
holidays
Programmable
Holiday Locations
6.
Enter the month of the holiday, then press ENTER.
7.
Enter the day of the month for the holiday, then press ENTER.
8.
Repeat steps 6 and 7 for any remaining holidays you wish to program.
9-23
Figure 9-11 Changing Day/Night Sensitivity Time
Figure 9-12 Edit Holidays Screen
151430-L8