Allow the appropriate space in front of C Series modules for cabling clearance, as shown in
the following figure. The different connector types on C Series modules require different
cabling clearances. For a complete list of cabling clearances for C Series modules, visit
ni.com/info
and enter the Info Code

Ambient Temperature

Measure the ambient temperature at each side of the NI 9154, 63.5 mm (2.50 in.) from the side
and 50.8 mm (2.00 in.) forward from the rear of the NI 9154, as shown in the following figure.
63.5 mm
(2.50 in.)
1
50.8 mm
(2.00 in.)
1. Location for measuring the ambient temperature

Mounting the Device on a DIN Rail

You can use the NI DIN rail mounting kit to mount the NI 9154 on a standard 35-mm DIN
rail.
What to Use
NI 9154
Screwdriver, Phillips #2
NI DIN rail mounting kit, 779018-01
DIN rail clip
M4x22 screw (x2)
crioconn
Figure 6. NI 9154 Cabling Clearance
Cabling
Clearance
Figure 7. NI 9154 Ambient Temperature Location
.
NI 9154 User Manual | © National Instruments | 9
63.5 mm
(2.50 in.)
1
50.8 mm
(2.00 in.)