9

Maintenance

9.1

Notes on safety for the maintenance

The periodic maintenance is essential for the good operation,
safety, yield and duration of the burner.
It allows you to reduce consumption and polluting emissions and
to keep the product in a reliable state over time.
The maintenance interventions and the calibration
of the burner must only be carried out by qualified,
authorised personnel, in accordance with the con-
tents of this manual and in compliance with the
DANGER
standards and regulations of current laws.
9.2

Maintenance programme

9.2.1
Maintenance frequency
The combustion system should be checked at
least once a year by a representative of the man-
ufacturer or another specialised technician.
9.2.2
Checking and cleaning
The operator must use the required equipment
during maintenance.
Combustion head
Open the burner and make sure that all components of the
combustion head are in good condition, not deformed by the
high temperatures, free of impurities from the surroundings
and correctly positioned.
Clean the combustion head in the fuel exit area, on the diffuser
disc.
Burner
Check for excess wear or loose screws and clean the outside of
the burner.
Fan
Check to make sure that no dust has accumulated inside the fan
or on its blades, as this condition will cause a reduction in the air
flow rate and provoke polluting combustion.
Flame sensor
Clean the flame sensor.
Electrodes
Check the correct position of electrodes
Nozzles
It is advisable to replace nozzles every year during regular
maintenance operations.
Do not clean the nozzle openings; do not even open them.
Maintenance
Before carrying out any maintenance, cleaning or checking oper-
ations:
Disconnect the electrical supply from the burner
by means of the main system switch.
DANGER
Turn off the fuel interception tap.
DANGER
Wait for the components in contact with heat
sources to cool down completely.
Filters
Check the filtering baskets on line and at nozzle present in the
system. Clean or replace if necessary.
If rust or other impurities are observed inside the pump, use a
separate pump to lift any water and other impurities that may
have deposited on the bottom of the tank.
Pump
Please check that the supply line and filters are clear. The use of
a pump vacuum gauge will assist in this. This measure permits
the cause of the anomaly to be traced to either the suction line or
the pump.
If the problem lies in the suction line, check to make sure that the
filter is clean and that air is not entering the piping.
Hoses
 Check periodically the flexible pipes conditions. They have
to be replaced at least every 2 years.
 In case of use of gas oil and bio fuel blends, it is strongly rec-
ommended to inspect even more frequently the hoses and
replace them where contamination has occurred.
 Check to make sure that the hoses are still in good condi-
tion.
The hoses supplied with this burner set for
Kerosene use are not suitable for use with Gas oil
containing a Bio blend.
WARNING
Please refer to the spare part list for the specific
hoses suitable for bio fuel use.
In case of use with gas oil containing up to 10%
Bio blend, it will be essential to use flexible oil
lines suitable for bio fuel use.
Please contact Riello for further information.
Fuel tank
If water or contamination is present within the fuel tank, it is es-
sential that this is removed before the equipment is to be used.
This is extremely important when gas oil containing Bio diesel is
in use. If in doubt about how to achieve this then please contact
the fuel or oil tank supplier.