6.6. Outdoor Unit Clearances - Multiple Units

Height of
Wall (C)
Unit
Height (A)
CLEARANCE NOTES FOR MULTIPLE UNITS:
If the height of the wall (C) is less than or equal to the height of the smallest unit (A),
the distance from the unit to the wall (B) must be a minimum of 10 inches (254 mm).
If 1/2 the height of the unit (A) is less than the height of the wall (C), the distance
from the unit to the wall (B) must be a minimum of 12 inches (305 mm).
If the height of the wall (C) is greater than the height of the unit (A), the distance
from the unit to the wall (B) must be a minimum of 20 inches (508 mm).
Figure 19. Multiple Outdoor Unit Clearances - Inches (mm)