Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury
or loss of life. Installation and service must be performed by a qualified installer or service agency.
Electric shock hazard. Can cause injury or death. Before attempting to perform any service or
maintenance, turn the electrical power to unit OFF at disconnect switch(es). Unit may have multiple
power supplies.
To prevent serious injury or death:
1- Lock-out/tag-out before performing maintenance.
2- If system power is required (e.g., smoke detector maintenance), disable power to blower, remove fan belt
where applicable, and ensure all controllers and thermostats are set to the "OFF" position before performing
maintenance.
3- Always keep hands, hair, clothing, jewelry, tools, etc., away from moving parts.
As with any mechanical equipment, contact with sharp sheet metal edges can result in personal injury. Take care
while handling this equipment and wear gloves and protective clothing.
1.

Safety Precautions

Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure the risk of
ignition is minimized.
Work in a controlled environment to minimize the risk of a flammable gas or vapor being present.
All maintenance staff and others working in the local area must be informed on the nature of work being completed
Avoid working in confined spaces.
Section off the area around the work space.
Ensure the conditions within the area have no flammable materials.

1.1. Refrigerant Presence

Use a refrigerant detector to verify the work area does not have flammable substances
Ensure the leak detection equipment is suitable for use with flammable refrigerants (i.e. no sparking, adequately
sealed or intrinsically safe)

1.2. Fire Extinguisher

If any hot work is required on the refrigeration equipment or any associated parts, appropriate fire extinguishing equipment
must be immediately available (such as a dry powder or CO2 fire extinguisher adjacent to the charging area).

1.3. No Ignition Sources

Do not use any sources of ignition while servicing the refrigeration system. Pipe work that contains or has contained
flammable refrigerant could lead to risk of fire or explosion if exposed to sources of ignition.
Prior to servicing the unit, survey the area around the equipment to ensure there are no flammable hazards or
ignition risks.
Keep all possible ignition sources (including cigarette smoking) away from the site during installation, repair, or
removal and disposal of refrigerant.
WARNING
WARNING
WARNING
CAUTION
WARNING