Connection Of The Power Cables - Fujitsu SE500 Basic Operating Manual

Hide thumbs Also See for SE500:
Table of Contents

Advertisement

Power supply

4.3.1 Connection of the power cables

Most of the hardware components in the SE server rack do not incorporate any switches
which disconnect them from the power source. Consequently the power cables of the
hardware components must be attached or detached when it is necessary to connect or
disconnect the components from the power source.
Figure 6: Example of a power distribution unit as used in the rack
v
32
CAUTION!
Equipment damage
All work on the power supply must be conducted by Customer Support.
Connect each power cable to a grounded service outlet located within the
operator's reach.
The power cables must be connected in such a manner that the power
consumption of the rack components does not exceed the maximum rated
current of the circuit's fuse and the maximum permissible current of the fuses in
the power distribution unit in the rack.
Free sockets in the power distribution unit may not be used to connect other
devices. The total permissible current for a power distribution unit could be
exceeded if other devices were connected.
If you have addition requirements, please contact Customer Support.
Racks
U41858-J-Z126-2-76

Advertisement

Table of Contents
loading

This manual is also suitable for:

Se700Bs2000Se300Se700bSe500bSe300b

Table of Contents