Possible causes
The preferential kWh rate power
supply settings and electrical
connections do NOT match
The preferential kWh rate signal
was sent by the electricity
company
12.2.3
Symptom: The pump is making noise
(cavitation)
Possible causes
There is air in the system
The water pressure at the pump
inlet is too low
12.2.4
Symptom: The pressure relief valve opens
Possible causes
The expansion vessel is broken
The water volume in the
installation is too high
The water circuit head is too high The water circuit head is the
ERLQ004~008CA + EHVH04+08S18CA3VF
Daikin Altherma low temperature split
4P3662261 – 2014.01
Corrective action
This should match with the
connections as explained in
"6.4.1 About preparing electrical
wiring" on page 24 and "7.6.4 To
connect the main power
supply" on page 37.
Wait for the power to return (2
hours max.).
Corrective action
Purge air manually (see
"9.3.1 To perform a manual air
purge" on page 61) or use the
automatic air purge function (see
"9.3.2 To perform an automatic
air purge" on page 62).
Check and make sure that:
▪ The water pressure is >1 bar.
▪ The manometer is not broken.
▪ The expansion vessel is not
broken.
▪ The prepressure setting of the
expansion vessel is correct
(see
"6.3.4 Changing the pre
pressure of the expansion
vessel" on page 23).
Corrective action
Replace the expansion vessel.
Make sure that the water volume
in the installation is below the
maximum allowed value (see
"6.3.3 To check the water
volume" on page 22 and
"6.3.4 Changing the prepressure
of the expansion vessel" on
page 23).
difference in height between the
indoor unit and the highest point
of the water circuit. If the indoor
unit is located at the highest
point of the installation, the
installation height is considered
0 m. The maximum water circuit
head is 10 m.
Check the installation
requirements.
12.2.5
Symptom: The water pressure relief valve
leaks
Possible causes
Dirt is blocking the water
pressure relief valve outlet
12.2.6
Symptom: The space is NOT sufficiently
heated at low outdoor temperatures
Possible causes
The backup heater operation is
not activated
The backup heater equilibrium
temperature has not been
configured correctly
12 Troubleshooting
Corrective action
Check whether the pressure
relief valve works correctly by
turning the red knob on the valve
counterclockwise:
▪ If you do NOT hear a clacking
sound, contact your dealer.
▪ If the water keeps running out
of the unit, close both the
water inlet and outlet shutoff
valves first and then contact
your dealer.
Corrective action
Check and make sure that:
▪ The backup heater operation
mode is enabled. Go to:
▪ [A.5.1.1] > Installer settings
> Heat sources > Backup
heater > Operation mode
OR
▪ [A.8] > Installer settings >
Overview settings [501]
▪ The thermal protector of the
backup heater has not been
activated. If it has, check:
▪ The water pressure
▪ Whether there is air in the
system
▪ The air purge operation
Press the reset button in the
switch box. See
"15.2 Components" on page 76
for the location of the reset
button.
Increase the "equilibrium
temperature" to activate the
backup heater operation at a
higher outdoor temperature. Go
to:
▪ [A.5.1.4] > Installer settings >
Heat sources > Backup heater
> Equilibrium temp. OR
▪ [A.8] > Installer settings >
Overview settings [500]
Installer reference guide