The energy management system (field supply) decides the activation
of a certain power limitation level. Example: To limit the maximum
power of the entire house (lighting, domestic appliances, space
heating...).
D
a
5
4
3
A8P
2
1
b
A
B
C
A
Outdoor unit
B
Indoor unit
C
DHW tank
D
Energy management system
a
Power limitation activation (4 digital inputs)
b
Backup heater
P
i
a
DI4
DI3
b
DI1
t
P
Power input
i
t
Time
DI
Digital inputs (power limitation levels)
a
Power limitation active
b
Actual power input
Setup
▪ Demand PCB (option EKRP1AHTA) needed.
▪ Maximum four digital inputs are used to activate the
corresponding power limitation level:
▪ DI1 = weakest limitation (highest energy consumption)
▪ DI4 = strongest limitation (lowest energy consumption)
▪ For the specification and the connection of the digital inputs, see
"15.4 Wiring diagram – components: Indoor unit" on page 81.
Configuration
Set the power consumption control settings in [A.6.3.1] via the user
interface (for the description of all settings, see "8 Configuration" on
page 41):
▪ Select activation by digital inputs.
▪ Select the type of limitation (power in kW or current in A).
▪ Set the desired power limitation level corresponding to each digital
input.
INFORMATION
In case more than 1 digital input is closed (at the same
time), the digital input priority is fixed: DI4 priority>...>DI1.
ERLQ004~008CA + EHVH04+08S18CA3VF
Daikin Altherma low temperature split
4P3662261 – 2014.01
5 Application guidelines
5.6.3
Power limitation process
The outdoor unit has better efficiency than the electrical heaters.
Therefore, the electrical heaters are limited and turned OFF first.
The system limits power consumption in the following order:
1
Limits the backup heater.
If... has priority
Space heating
2
Turns OFF the backup heater.
3
Limits the outdoor unit.
4
Turns OFF the outdoor unit.
5.7
Setting up an external temperature
sensor
You can connect one external temperature sensor. It can measure
the indoor or outdoor ambient temperature. Daikin recommends to
use an external temperature sensor in the following cases:
Indoor ambient temperature
▪ In room thermostat control, the user interface is used as room
thermostat and it measures the indoor ambient temperature.
Therefore, the user interface must be installed on a location:
▪ Where the average temperature in the room can be detected
▪ That is NOT exposed to direct sunlight
▪ That is NOT near a heat source
▪ That is NOT affected by outside air or air draught because of,
for example, door opening/closing
▪ If this is NOT possible, Daikin recommends to connect a remote
indoor sensor (option KRCS011).
▪ Setup: For installation instructions, see the installation manual of
the remote indoor sensor.
▪ Configuration: Select room sensor [A.2.2.B].
Outdoor ambient temperature
▪ In the outdoor unit, the outdoor ambient temperature is measured.
Therefore, the outdoor unit must be installed on a location:
▪ At the north side of the house or at the side of the house where
the most heat emitters are located
▪ That is NOT exposed to direct sunlight
▪ If this is NOT possible, Daikin recommends to connect a remote
outdoor sensor (option EKRSCA1).
▪ Setup: For installation instructions, see the installation manual of
the remote indoor sensor.
▪ Configuration: Select outdoor sensor [A.2.2.B].
▪ During suspend (see
"8 Configuration" on page
unit is turned down to reduce the standby energy losses. As a
result, the outdoor ambient temperature is NOT read out.
▪ If the desired leaving water temperature is weather dependent, the
full time outdoor temperature measurement is important. This is
another reason to install the optional outdoor ambient temperature
sensor.
INFORMATION
The external outdoor ambient sensor data (either averaged
or instantaneous) is used in the weatherdependent control
curves. To protect the outdoor unit, the internal sensor of
the outdoor unit is always used.
Then set the heater priority
via the user interface to...
Backup heater.
41), the outdoor
Installer reference guide
19