Clock, Schedule, Setpoints, and Options
Specifications
Sensor Resolution
6
Defines the time and date used with the programmable time schedule
function:
• Time format:
– AM-PM: 12 hour format. (Displays as 8:00 PM)
– 24 Hours: 24 hour format. (Displays as 20:00 hours)
• Time – defines the hour and minute of the current day.
Clock
• Year – defines the current year.
• Month – defines the current month.
• Day – defines the current day of the month.
Weekday – displays a day of the week corresponding to the date
entered into the sensor.
Defines the time values that are used to determine when to transition
from the current occupancy state to the next state.
Schedule
Three occupied/unoccupied event pairs are supported. Setting an event
to a time value enables the event. Setting the event to - - : - - disables the
event.
Defines the following:
• Unocc. cool – the temperature setpoint in use when the equipment is
in cooling mode and occupancy mode is unoccupied.
• Occ. cool – the temperature setpoint in use when the equipment is in
cooling mode and occupancy mode is occupied.
• Occ. heat – the temperature setpoint in use when the equipment is in
Setpoints
heating mode and occupancy mode is occupied.
• Unocc. heat – the temperature setpoint in use when the equipment is
in heating mode and occupancy mode is unoccupied.
(50.0°F to 90.0°F [10.0°C to 32.2°C])
Defines the occupancy commands and schedule type.
• Occupancy cmd
– Loc. occ.: occupancy is determined by the schedule.
– Occupied: force occupied mode.
Options
– Unocc.: force unoccupied mode.
• Schedule type
– 7 days: each day of the week.
– 5+2: weekdays + weekend.
– 5+1+1: weekdays + Saturday + Sunday.
Sensor Operating
32°F to 122°F (0°C to 50°C)
Temperature
Storage
- 22°F to 122°F (- 30°C to 50°C)
Temperature
Storage and
Operating
0% to 95%, non-condensing
Humidity Range
Temperature
+/- 0.9°F (+/- 0.5°C) @ 70F (21°C) typical calibrated
Control Accuracy
Temperature
+/- 0.2°F (+/- 0.1°C)
Room Air
Temperature
- 40°F to 122°F (- 40°C to 50°C)
Display Range