Generac Power Systems Power Zone Pro Owner's Manual page 23

Main controller
Table of Contents

Advertisement

Pin
Name
(BS5) J5-1
DIN1
(BS5) J5-2
DIN2
DIN3
(BS5) J5-3
(BS5) J5-4
DIN4
(BS5) J5-5
DIN5
(BS5) J5-6
DIN6
(BS5) J5-7
DIN7
(BS5) J5-8
DIN8
DIN9
(BS5) J5-9
DIN10
(BS5) J5-10
DIN11
(BS5) J5-11
DIN12
(BS5) J5-12
DIN13
(BS5) J5-13
DIN14
(BS5) J5-14
DIN15
(BS5) J5-15
(BS5) J5-16
N.C.
Owner's Manual for Power Zone Pro Main Controller
Table 3-5. J5 Connector
Description
Digital Input. Configurable
Digital Input. Configurable
Digital Input. Configurable
Digital Input. Configurable
Digital Input. Configurable
Digital Input. Configurable
Digital Input. Configurable
Digital Input. Configurable
Digital Input or PWMI 0.
Configurable
Digital Input or PWMI 1.
Configurable
Digital Input or PWMI 2.
Configurable
Digital Input or PWMI 3.
Configurable
Digital Input or PWMI 4.
Configurable
Digital Input or PWMI 5.
Configurable
Digital Input or PWMI 6.
Configurable
No Connection
Installation and Operation
Configured Default
NA = Not Configurable
Auto Switch
Manual Switch
Ruptured Basin/Gas
Pressure
E-Stop
2-wire Remote Start
Battery Charger AC Fail
Aux In #3 (Line Power)
Aux In #4 (Gen Power)
Aux In #1 PWMI #0
Aux In #2 PWMI #1
Aux In #5 PWMI #2
Aux In #6 PWMI #3
Aux In #7 PWMI #4
Aux In #8 PWMI #5
AVR ZC - PWMI #6
Wire # (Default)
174
175
601
R15
183
505
DI3
DI4
DI1
DI2
DI5
DI6
DI7
DI8
406
19

Hide quick links: