Selecting The Domestic Hot Water Cylinder; Selecting A Low Loss Header - Vaillant ecoTEC plus VC 406/5-5 Installation And Maintenance Instructions Manual

Table of Contents

Advertisement

In order to control the cylinder's post-heating, connect
a VR 10 temperature sensor or a thermostat to the plug
that is connected to the main PCB.
Wiring diagram (→ Page 47)
Set diagnostics code D.026 to 1.
Overview of diagnostics codes (→ Page 39)
5.1.5
Basic system diagram type 5: Cascade with
two to seven boilers + a cylinder that is
connected to the heating circuit
1
Wall-hung boiler with
internal pump
2
Heating circuits
3
Low loss header or
plate heat exchanger
The product can control a cascade system.
Number for
Control
the basic
system
diagram
0020259033
VRC 700
system
control
VR 71 multi-
functional
module
The settings for the internal pump are made at the factory.
Ensure that there is sufficient dimensioning for the
connections and the domestic hot water cylinder.
(→ Page 13)
Downstream of the low loss header, select a domestic
hot water pump that is suitable for the domestic hot water
cylinder.
Connect the pump for the decoupled domestic hot water
circuit to the plug X13 for the main PCB.
Connect the temperature sensor for the low loss header
to plug X41 on the main PCB. Observe the instructions
for the low loss header.
0020261188_00 ecoTEC plus Installation and maintenance instructions
1
2
3
6 4
5
6
4
External pump for the
decoupled domestic hot
water circuit
5
External domestic hot
water circulation pump
6
Domestic hot water
cylinder
Number
Wiring
of cir-
cuits
>3
See the instructions
for the system con-
trol.
In order to control the cylinder's post-heating, connect
a VR 10 temperature sensor or a thermostat to the plug
that is connected to the main PCB.
Wiring diagram (→ Page 47)
Set diagnostics code D.026 to 1.
Overview of diagnostics codes (→ Page 39)
5.2

Selecting the domestic hot water cylinder

The product can control an optional domestic hot water cylin-
der (recommended option for products with an output below
50 kW).
Use a low loss header for products that are connected to
a domestic hot water cylinder and have a domestic hot
water output requirement of over 50 kW, . (→ Page 13)
Use the following components to connect the domestic
hot water cylinder:
Domestic hot water cylinder
VC 406/5-5 (E-DE)
VC 406/5-5 (LL-DE)
VC 476/5-5 (E-DE)
VC 476/5-5 (LL-DE)
VC 636/5-5 (E-DE)
VC 636/5-5 (LL-DE)
5.3

Selecting a low loss header

The low loss header disconnects the heat generator hydraul-
ically from the heating system. This prevents feed head in-
teractions between the individual circulation pumps. Further-
more, the low loss header ensures that a sufficient minimum
volume of water continuously circulates through the heat
generator.
Observe the information on treating heating water.
(→ Page 19)
If you cannot guarantee the conditions for treating
the heating water, install an external plate heat ex-
changer to protect the product.
Low loss header
VC 406/5-5 (E-DE)
VC 406/5-5 (LL-DE)
VC 476/5-5 (E-DE)
VC 476/5-5 (LL-DE)
VC 636/5-5 (E-DE)
VC 636/5-5 (LL-DE)
Observe the instructions for the low loss header.
You do not require any electronic accessories when using
a low loss header. You can connect simple installations dir-
ectly inside the electronics box.
Observe the wiring diagram.
Installation 5
Cylinder
Internal dia-
meter of the
connection
VIH R 300
20 mm
VIH R 300
20 mm
VIH R 300
20 mm
VIH R 300
20 mm
VIH R 500
25 mm
VIH R 500
25 mm
Heating system spread
10 K
15 K
20 K
WH 95
WH 40-2
WH 40-2
WH 95
WH 40-2
WH 40-2
WH 95
WH 40-2
WH 40-2
WH 95
WH 40-2
WH 40-2
WH 160
WH 95
WH 40-2
WH 160
WH 95
WH 40-2
13

Advertisement

Table of Contents
loading