Introduction; Application; Electrical Ratings - Johnson Controls GS Series Manual

Single-block multi-function gas control valves
Table of Contents

Advertisement

Introduction

The UL Listed GS Series single-block multi-function gas control valves

Application

are intended for use on atmospheric and forced-draft gas burners in heating
installations. This multi-functional control on a single-block valve body
provides a compact answer to gas train applications. The GS valve
replaces multiple gas train components, such as on/off gas valves, gas
pressure regulators, and modulating gas valves. Optional sizing of body
flanges offers greater adaptation to diversified burner designs and
applications. Valves are approved to North American and European gas
valve standards, including UL 429.
Typical applications include boilers, burners and ovens, rooftop units,
makeup air heaters, hot water heaters, kilns, and paint booths.
Electrical
Table 1: Electrical Ratings
Ratings
G—UL Listed GS-20/25 and GS-40/45 Series Single-block Multi-function Gas Control Valves Technical Bulletin 3
All manuals and user guides at all-guides.com
Figure 1: UL Listed GS Series Single-block
Multi-function Control Valves
Valve Model
Operating Voltages
GS-2_ _ _
230 VAC +10/-15%, 50/60 Hz
120 VAC +10/-15%, 50/60 Hz
24 VAC +10/-15%, 50/60 Hz
GS-4_ _ _
230 VAC +10/-15%, 50/60 Hz
120 VAC +10/-15%, 50/60 Hz
24 VAC +10/-15%, 50/60 Hz
Power Consumption
23 VA
23 VA

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gs-20 seriesGs-25 seriesGs-40 seriesGs-45 series

Table of Contents