Samsung MIM-E03CN Installation Manual page 44

Air to water heat pump
Hide thumbs Also See for MIM-E03CN:
Table of Contents

Advertisement

Troubleshooting
Water pump & Flow Sensor
Display
E911
Water pump ON ( Low flow rate ) : NOT enough water flow
Water flow < 12LPM(Outdoor unit capacity > 9kW)
Water flow < 7LPM(Outdoor unit capacity ≤ 9kW)
Water flow < 7LPM(AE080/120/140BXYD**)
E912
Water pump OFF ( Normal flow rate )
Water flow > 12LPM(Outdoor unit capacity > 9kW)
Water flow > 7LPM(Outdoor unit capacity ≤ 9kW)
Water flow > 7LPM(AE080/120/140BXYD**)
44
Low flow rate error
• in case of low flow rate in 30 sec during water pump signals is ON(Starting)
• in case of low flow rate in 15 sec during water pump signals is ON(After starting)
Normal flow rate error
• in case of normal flow rate in 10min during water pump signal is OFF
Explanation