Lennox ELITE 12GCS Series Unit Information page 13

Hide thumbs Also See for ELITE 12GCS Series:
Table of Contents

Advertisement

Mode of
Common
Operation
Motor Plug in
Pin 1
Terminals
24 V motor wire
Blue
Cooling
X
Continuous Fan
X
Heat Pump
X
Aux Heat (stage two)
X
Aux Heat (stage two)
X
Emergency Heat
X
Defrost Tempering
X
Heat
NOTES:
Pins not used 4, 6, 7, 8, 13, 16
All motor times are approximate.
At start up, the motor runs at 82% of air flow for 7.5 minutes, then ramps up to 100%
At shut down, the motor runs at 94%of air for 60 seconds before a 30 second ramp off.
Continuous fan is 31% of total CFM−transition time from continuois fan to heat/cool air flow is 20 seconds.
SPEED CHANGES:
To increase COOLING CFM by 5%: Cut violet wire (PIN 5) to motor and tape off ends.
To increase HEATING CFM by 5%: Cut pink wire (PIN 11) to motor and tape off ends.
The above changes will increase the continuous fan speed to 620 CFM.
HUMIDITY CONTROL
The CFM of the motor can be reduced by 15% by wiring a standard humidity contol in series with the TAN (PIN 10) wire. The humidity control
must be closed when the humidity is below its setpoint and open when the humidity is above its setpoint. When the humidity control opens,
R is interupted to PIN 10 and the CFM is reduced 15% from full speed.
12CHP060 with Variable Speed Motor
W1
Common
R
O
Pin 2
Pin 3
Pin 5
Pin 9
Orang
White
Lt Blue
Violet
e
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
TABLE 3
R
R
R
Y
Pin 10
Pin 11
Pin 12
Pin 14
Tan
Pink
Red
Yellow
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Ramp
Ramp
Ramp
G
up
up
down
After 7.5
25 Sec
2 Sec
Min
Pin 15
CFM
CFM
CFM
Green
82%
100%
94%
X
1558
1900
1786
X
590
590
590
X
1558
1900
1786
X
1558
1900
1786
X
1558
1900
1786
X
1558
1900
1786
X
Ramp
down
90 Sec
CFM
0%
0
0
0
0
0
0