Bosch WORCESTER Greenstar CDi Classic Series Technical Information page 49

Gas-fired condensing wall mounted boiler range
Table of Contents

Advertisement

Option 1: Minimum height
500mm
Flat roof
300mm
Components
Part No. 100mm
Part No. 125mm
Maximum lengths (mm) & no. of components required
Greenstar 29CDi Classic
100mm
1,090
125mm
1,365
Greenstar 34CDi Classic
100mm
1,090
125mm
1,365
Greenstar 38CDi Classic
100mm
1,090
125mm
1,365
Greenstar 42CDi Classic
100mm
1,090
125mm
1,365
Greenstar CDi Compact and Si Compact series
100mm
1,090
125mm
1,365
Greenstar i Junior series
100mm
1,090
125mm
1,365
Note: The short fl ue extension (100mm dia.)
may be used as an alternative to the standard
extension as required up to the maximum fl ue
lengths stated (Part No. 7 716 191 133).
100mm dia. 1,090mm
L =
125mm dia. 1,365mm
7 719 002 430
7 719 002 431
1
1
1
1
1
1
1
1
1
1
1
1
Option 2: Vertical balanced fl ue system maximum height
500mm
300mm
Components
Part No. 100mm
7 719 002 430
Part No. 125mm
7 719 002 431
Maximum lengths (mm) & no. of components required
Greenstar 29CDi Classic
100mm
9,400
125mm 18,500
Greenstar 34CDi Classic
100mm
8,000
125mm 16,000
Greenstar 38CDi Classic
100mm
7,500
125mm 16,000
Greenstar 42CDi Classic
100mm
7,500
125mm 16,000
Greenstar CDi Compact and Si Compact series
100mm
6,000
125mm 15,000
Greenstar i Junior series
100mm
6,400
125mm 15,000
Note: The maximum fl ue length must be reduced by the
following amounts for each bend used.
Greenstar CDi Classic
60/100mm fl ues
Greenstar CDi Classic
80/125mm fl ues
Greenstar CDi Compact and
Si Compact – all fl ue sizes
Greenstar i Junior
– all fl ue sizes
Flat roof
7 716 191 083
7 719 003 666
1
up to 9
1
up to 18
1
up to 8
1
up to 16
1
up to 7
1
up to 16
1
up to 7
1
up to 16
1
up to 5
1
up to 14
1
up to 6
1
up to 14
45º bend
90º bend
750mm
1,500mm
1,000mm
2,000mm
1,000mm
2,000mm
1,000mm
2,000mm
49