Bosch WORCESTER Greenstar CDi Classic Series Technical Information page 27

Gas-fired condensing wall mounted boiler range
Table of Contents

Advertisement

930mm
Using 100mm
5mm
flue kit
– 1,080mm
Using 125mm
flue kit
20mm to
– 1,110mm
removable
door
600mm front
clearance
for service
Clearances for Greenstar i Junior
Boiler location
The appliance may be installed in any room, although
particular attention is drawn to the requirements of the
IEE regulations applicable, and in Scotland the electrical
provisions with respect to installation in a room containing
a bath or shower.
1. The room in which the appliance is installed does not
require a purpose-provided air vent.
2. If the appliance is installed in a cupboard or
compartment with dimensions that allow the following
minimum clearances, then no ventilation is required:
Compartment installation
Minimum unventilated clearance
Greenstar
Position of
CDi Classic
appliance
In front
20mm
Below
200mm
Right side
5mm
Left side
5mm
Above
30mm
fl ue elbow
*This can be reduced to 50mm for one side, provided that the total side
clearances add up to 400mm or more.
410mm
+30mm
above elbow
5mm
200mm
(to removable door)
Greenstar
Greenstar
CDi Compact
i Junior
& Si Compact
20mm
100mm
200mm
200mm
5mm
200mm*
5mm
200mm*
30mm
30mm
Ventilation-free compartment installation – minimum clearances
200mm*
100mm to
removable door
600mm front
clearance for
service
Greenstar i Junior
*This can be reduced to 50mm for one side, provided that the total side
clearances add up to 400mm or more.
+30mm
above elbow
200mm*
200mm
27
27