0176 (B) Subject to change without prior notice PRESSURE INDEPENDENT AUTOMATIC INSTRUCTIONS BALANCING AND ROTARY CONTROL VALVE European Single Point of Contact: JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY. NA/SA Single Point of Contact: JOHNSON CONTROLS 507 E MICHIGAN ST...
Page 2
PRESSURE READING FOR VERIFICATIONS IF P1-P2 > START UP PRESSURE THEN THE VALVE IS WITHIN THE WORKING RANGE START UP PRESSURE Q≠CONST Q=CONST P1-P2 30 kPa P1 = pressure port P2 = pressure port During cleaning operation of the valve use a damp cloth, DO NOT use any detergent or chemical solvent that could seriously damage the parts.
Page 3
5400 1.50 Johnson Controls does not accept any liability for improper or wrong use of this product. Always protect the pressure regulator by using strainers upstream of the valve and, in any case, make sure water quality complies with UNI 8065 standards (Fe < 0.5 mg/kg and Cu < 0.1 mg/Kg).
Page 4
CONTROL VALVE ACTUATORS Actuator assembly with pre-setting device on. For the calibration of the VA9310 proceed as follow: Calibration (CAL) Function actuators The Calibration function enables the actuator to redefine the valid for VA9208-GGx-1 Series selected input signal range proportionally across a reduced rotation range.