Section 8 - Service Information; Ratings - Weil-McLain SVF 500 Manual

Commercial condensing gas-fired water boilers
Hide thumbs Also See for SVF 500:
Table of Contents

Advertisement

svf
series
500/600
Service Information
Section Contents

Ratings

Read Configuration Settings
Ratings
Table 26
Ratings and engineering data
DOE
Minimum
Maximum
Input -
Input
Natural
Boiler
Gas
Model
Number
Btuh
Btuh
(Note 1)
(Note 1)
SVF 500
500000
50000
SVF 600
600000
50000
1
Ratings shown are for sea level applications only. For altitudes above sea level, the SVF boiler requires no modifications; it automatically derates itself by
approximately 4% per 1,000 ft above sea level For elevations over 2,000 ft , see the High Altitude section on page 114 for required control parameter changes The
length of the vent and air piping will affect the maximum input. See Table 27 below for derate % according to vent and air piping length.
2
Net AHRI ratings are based on net installed radiation of sufficient quantity for the requirements of the building, and nothing needs to be added for normal piping and
pickup Ratings are based on a piping and pickup allowance of 1 15 An additional allowance should be made for unusual piping and pickup loads
3
Thermal efficiency is based on AHRI testing procedure AHRI 1500.
4
SVF boilers can be direct vent or direct exhaust vented, either through a side wall or through the roof, as instructed in this manual and compliant with all local codes
SVF boilers require special venting, consistent with Category IV boilers For Category II boiler systems, see pages 30 to 33 Use only the vent materials and
methods identified in this manual.
5
The values are for the stack flow rate at the maximum firing rate for the given boiler. The values can vary, depending on the location of the installation and the
operating conditions
Table 27
Derate due to vent and air piping length
Boiler Model
Derate % for Direct Exhaust
SVF 500/600
550-100-273/0523
boiler manual
1
SeCTion 8
AHRI Certified Ratings
Minimum
Input -
Gross
Net
Propane
Output
Rating
Gas
Btuh
Btuh
Btuh
(Note 1)
(Note 1)
(Note 2)
50000
490000
426000
50000
588000
511000
Determine vent/air piping equivalent length (ft.) - Use the length for L in the equations.
% Derate = L x 077
Example: If L = 75 ft.,
Derate % = 75 x .077 = 5.775
serviCe informaTion
Maintenance Log
139
Installation and Service Certificate
140
Notes
Boiler
Thermal
Vent/Air
Water
Efficiency
Pipe Size
Content
%
Inches
Gallons
(Note 3)
(Note 4)
98 0
12 4
4
98 0
12 4
4
Notes
Derate % for Direct Vent
Derate % = 75 x .074 = 5.550
Stack/Vent
Boiler Weight
Flow Rate
(pounds)
Dry
Operating
scfm
Weight
Weight
(Note 5)
(no water)
(filled)
105
468
571
125
468
571
% Derate = L x 074
Example: If L = 75 ft.,
1
2
142
143
143
3
4
Shipping
Weight
5
611
611
6
7
8
139

Advertisement

Table of Contents
loading

This manual is also suitable for:

Svf 600

Table of Contents