Typical Chimney Connections; Horizontal Air Inlet, Outlet And Chimney Connections; Outside And Ambient Combustion Air; Free Area - York FC8T-UH Manual

High efficiency tubular heat exchanger
Table of Contents

Advertisement

272312-UIM-A-0407
CHIMNEY OR
GAS VENT
FIGURE 24: Typical Chimney Connections
FIGURE 25: Horizontal Air Inlet, Outlet and Chimney Connections
GAS
VENT
GABLE
VENT
VENTILATED
ATTIC
OPTIONAL
TOP ABOVE
INLET (a)
INSULATION
OUTLET
SOFFIT
AIR (a)
VENT
GAS
WATER
HEATER
VENTILATED
CRAWL SPACE
5. A square or rectangular shaped duct shall onl be used
when the required free area of the suppl opening is
2
2
9 in (58.06 cm ) or larger. When a square or rectangular
duct is used, its small dimensionshall not be less than
3 in (7.6 cm).
6. An air inlet suppl from outdoors shall be equipped with
a means to prevent the direct entr of rain and wind.
Such means shall not reduce the required free area of
the air suppl opening.
7.
An air suppl inlet opening from the outdoors shall
be located not less than 12" (30.5 cm) above the
outside grade level.
FIGURE 26: Outside and Ambient Combustion Air
20
OPENING
OPENING
OUTLET
AIR DUCT
INLET
AIR DUCT
AIR SUPPLY OPENINGS AND DUCTS
1. An opening ma be used in lieu of a duct to provide to provide the outside air
suppl to an appliance unless otherwise permitted b the authorit having
jurisdiction. The opening shall be located within 12" (30.5 cm) horizontall from,
the burner level of the appliance. Refer to "COMBUSTION AIR SOURCE FROM
OUTDOORS and VENT AND SUPPLY AIR SAFETY CHECK" in these
instructions for additional information and safet check procedure.
2. The duct shall be either metal, or a material meeting the class 1
requirements of CAN4-S110 Standard for Air Ducts.
3. The duct shall be least the same cross-sectional area as the free
area of the air suppl inlet opening to which it connects.
4. The duct shall terminate within 12 in (30.5 cm) above, and
within 24 in (61 cm) horizontall from, the burner level of
the appliance having the largest input.
GABLE
VENT
VENTILATED
ATTIC
TOP ABOVE
INSULATION
SOFFIT
VENT
GAS
WATER
HEATER
INLET
AIR (b)
When a Category I furnace is removed or replaced, the original
venting system may no longer be correctly sized to properly vent
the attached appliances.
An improperly sized vent system can cause CARBON MONOXIDE
to spill into the living space causing personal injury, and or death.
TABLE 11: Free Area
Minimum Free Area Required for Each Opening
Combined
BTUH Input
Horizontal Duct
Rating For
(2,000 BTUH /
All Appliances
Sq. In.)
2
40,000
20 in
(129 cm
2
60,000
30 in
(193 cm
2
80,000
40 in
(258 cm
2
100,000
50 in
(322 cm
2
120,000
60 in
(387 cm
EXAMPLE: Determining Free Area - Vertical Minimum Duct Size
Appliance 1 Appliance 2
Total Input
+ 30,000 = 130,000 ÷ 4,000 = 32.5 Sq. In.
100,000
EXAMPLE: Determining Free Area - Horizontal Minimum Duct Size
Appliance 1 Appliance 2
Total Input
+ 30,000 = 130,000 ÷ 2,000 = 65 Sq. In.
100,000
TABLE 12: Unconfined Space Minimum Area in Square Inch
Minimum Free Area in Square Feet
BTUH Input Rating
40,000
60,000
80,000
100,000
120,000
OUTLET
AIR (b)
INLET
AIR (b)
COMBUSTION AIR SOURCE FROM OUTDOORS
1. Two permanent openings, one within 12 in (30.5 mm) of the top and
GAS
one within 12 in (30.5 mm) of bottom of the confined space,
VENT
permanent openings,
with the outdoors, crawl spaces or attic spaces.
2. One permanent openings, commencing within 12 in (30.5 mm)of the
top of the enclosure shall be permitted where the equipment has
clearances of at least 1 in (2.54 cm) from the sides and back and
6 in (15.24 cm) from the front of the appliance. The opening shall
communicate directl with the outdoors and shall have a minimum
free area of:
a.
1 square in per 3000 Btu per hour (6.45 cm
total input rating of all equipment located in the enclosure.
b.
Not less than the sum of all vent connectors in the confined space.
3. The duct shall be least the same cross-sectional area as the free
area of the air suppl inlet opening to which it connects.
4. The blocking effects of louvers, grilles and screens must be given
INLET
consideration in calculating free area. If the free area of a specific
AIR (a)
louver aor grille is not known.
Vertical Duct or
Round Duct
Opening to Outside
(4,000 BTUH /
(4,000 BTUH /
Sq. In.)
Sq. In.)
2
2
2
4" (10 cm)
)
10 in
(64 cm
)
2
2
2
5" (13 cm)
)
15 in
(97 cm
)
2
2
2
5" (13 cm)
)
20 in
(129 cm
)
2
2
2
6" (15 cm)
)
25 in
(161 cm
)
2
2
2
7" (18 cm)
)
30 in
(193 cm
)
Required for Each Opening
2
40 (258 cm
)
2
60 (387 cm
)
2
80 (516 cm
)
2
100 (645 cm
)
2
120 (774 cm
)
GAS
VENT
OUTLET
AIR (a)
GAS
WATER
HEATER
INLET
AIR (a)
shall communicate directl or b means of ducts
3
per
0.879 kW) of the
Unitary Products Group
Two