Checkout; Troubleshooting; Rtu Open Controller (Factory Option); Controller Options - Bryant Preferred Series Installation Instructions Manual

Single package rooftop
Hide thumbs Also See for Preferred Series:
Table of Contents

Advertisement

CHECKOUT

Inspect all wiring connections at the economizer module's ter-
minals, and verify compliance with the installation wiring dia-
grams. For checkout, review the Status of each configured pa-
rameter and perform the Checkout tests.
NOTE: For information about menu navigation and use of the
keypad see Interface Overview on page 31.
WARNING
ELECTRIC SHOCK HAZARD
Failure to follow this warning could result in personal injury,
property damage, or death.
Before performing service or maintenance operations on unit,
always turn off main power switch to unit and install lock(s)
and lockout tag(s). Unit may have more than one power
switch. Ensure electrical service to rooftop unit agrees with
voltage and amperage listed on the unit rating plate.
If any wiring changes are required, first be sure to remove
power from the economizer module before starting work. Pay
particular attention to verifying the power connection (24 vac).
Power Up
After the W7220 module is mounted and wired, apply power.
Initial Menu Display
On initial start up, Honeywell displays on the first line and
economizer W7220 on the second line. After a brief pause, the
revision of the software appears on the first line and the second
line will be blank.
Power Loss (Outage or Brownout)
All setpoints and advanced settings are restored after any pow-
er loss or interruption.
NOTE: All settings are stored in non-volatile flash memory.
Status
Use the Status menu (see Table 10) to check the parameter val-
ues for the various devices and sensors configured.
NOTE: For information about menu navigation and use of the
keypad, see Interface Overview on page 31.
Checkout Tests
Use the Checkout menu (see page 36) to test the damper opera-
tion and any configured outputs. Only items that are config-
ured are shown in the Checkout menu.
NOTE: For information about menu navigation and use of the
keypad, see Interface Overview on page 31.
To perform a Checkout test:
1.
Scroll to the desired test in the Checkout menu using the ▲
and ▼ buttons.
2.
Press the
(Enter) button to select the item. RUN?
appears.
3.
Press the
(Enter) button to start the test. The unit pauses
and then displays IN PROGRESS. When the test is complete,
DONE appears.
4.
When all desired parameters have been tested, press the
(Menu Up/Exit) button to end the test.
The Checkout tests can all be performed at the time of installa-
tion or at any time during the operation of the system as a test
that the system is operable.
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage.
Be sure to allow enough time for compressor start-up and
shutdown between checkout tests so that you do not short-
cycle the compressors.

TROUBLESHOOTING

Alarms
The economizer module provides alarm messages that display
on the 2-line LCD.
NOTE: Upon power up, the module waits 60 minutes before
checking for alarms. This allows time for all the configured devic-
es (e.g. sensors, actuator) to become operational. The exception is
the SAT sensor which will alarm immediately.
If one or more alarms are present and there has been no keypad
activity for at least 5 minutes, the Alarms menu displays and
cycles through the active alarms.
You can also navigate to the Alarms menu at any time.
Clearing Alarms
Once the alarm has been identified and the cause has been
removed (e.g. replaced faulty sensor) the alarm can be cleared
from the display.
To clear an alarm, perform the following:
1.
Navigate to the desired alarm.
2.
Press the
(Enter) button. ERASE? displays.
3.
Press the
(Enter) button. ALARM ERASED displays.
4.
Press the
(Menu Up/Exit) button to complete the action
and return to the previous menu.
NOTE: If the alarm still exists after clearing it, it is redisplayed
within 5 seconds.

RTU Open Controller (Factory Option)

For details on operating 581K*04-06F/K units equipped with
the factory-installed RTU Open controller option, refer to the
Factory-Installed Option RTU Open Multi-Protocol Controller
Controls, Start-Up, Operation and Troubleshooting manual.

Controller Options

LOW AMBIENT

If the unit comes with Electro-Mechanical (EM) control, then
no adjustment is necessary.
If the unit comes with the RTU Open controller option, then re-
fer to its installation control manual for details on adjusting
"Cooling Lock-Out" setting and configure for the specific job
requirements.

Smoke Detectors

Smoke detectors are available as factory-installed options on
581K***F/K models. Smoke detectors may be specified for
supply air only, for return air without or with economizer, or in
combination of supply air and return air. Return-air smoke de-
tectors are arranged for vertical return configurations only. All
components necessary for operation are factory-provided and
mounted. The unit is factory-configured for immediate smoke
detector shutdown operation; additional wiring or modifica-
tions to unit control board may be necessary to complete the
unit and smoke detector configuration to meet project require-
ments.
Units equipped with factory-optional return-air smoke detec-
tors require a relocation of the sensor module at unit installa-
tion. See Fig. 52 for the as-shipped location.
41