2Sp H/C (2 Speed Heat/Cool) Fan Operation; Speed Fan Operation (Single Phase Units Only) - Bryant Preferred Series Installation Instructions Manual

Single package rooftop
Hide thumbs Also See for Preferred Series:
Table of Contents

Advertisement

2SP H/C (2 SPEED HEAT/COOL) FAN OPERATION

FAN TYPE = 2SP H/C is not used on 581K***F/K units.

3 SPEED FAN OPERATION (SINGLE PHASE UNITS ONLY)

The W7220 controller does not actually control the fan speed
or the heat output of the unit, and only uses this information to
help determine the damper position. On single phase units, the
unit control board (UCB) will reduce the fan speed during
heating when the configured fan speed is set outside the opti-
mized heating speed window. If the job site application forces
DEMAND
OUTSIDE AIR
CONTROLLED
GOOD TO
VENTILATION
ECONOMIZE
(DCV)
NO
NONE
YES
NO
Below CO
Set
2
YES
NO
Above CO
Set
2
YES
*With stage 3 delay (STG3 DLY) in Advanced setup, COOL Y2-OUT will be turned ON after the delay time specified.
N/A = Not applicable
Table 14 — Economizer Operation - FAN TYPE = 3SPEED
INPUTS
W
COOL
(HEAT ON)
Y1-IN
ON
N/A
OFF
OFF
OFF
ON
OFF
ON
ON
N/A
OFF
OFF
OFF
ON
OFF
ON
ON
N/A
OFF
OFF
OFF
ON
OFF
ON
ON
N/A
OFF
OFF
OFF
ON
OFF
ON
ON
N/A
OFF
OFF
OFF
ON
OFF
ON
ON
N/A
OFF
OFF
OFF
ON
OFF
ON
this reduction in fan speed during heat, the economizer FAN
TYPE must be set to keep the appropriate outside air intake.
On single phase 581K***F/K units, if reduced the heating fan
speed is lower than the high cooling speed and higher than the
low cooling speed, hence the medium speed name. The econo-
mizer FAN TYPE needs to be set to 3SPEED (3 speed). This
indicates that the heating fan speed is between the Low cool/
vent fan speed and the High cool speed. Refer to Table 14 for
economizer operation.
FAN SPEED
COOL
COOL
COOL
Y2-IN
Y1-OUT
Y2-OUT
N/A
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
ON
ON
N/A
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
OFF*
N/A
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
ON
ON
N/A
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
OFF*
N/A
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
ON
ON
N/A
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF*
ON
ON
OFF*
40
OUTPUTS
DAMPER POSITION
(reference
OCCUPIED
only)
MEDIUM
MIN POS M
LOW
MIN POS L
LOW
MIN POS L
HIGH
MIN POS H
MEDIUM
MIN POS M
LOW
MIN POS L
MIN POS L to
LOW
Full Open
MIN POS H to
HIGH
Full Open
MEDIUM
VENTMIN M
LOW
VENTMIN L
LOW
VENTMIN L
HIGH
VENTMIN H
MEDIUM
VENTMIN M
LOW
VENTMIN L
VENTMIN L to
LOW
Full Open
VENTMIN H to
HIGH
Full Open
VENTMIN M to
MEDIUM
VENTMAX M
VENTMIN L to
LOW
VENTMAX L
VENTMIN L to
LOW
VENTMAX L
VENTMIN H to
HIGH
VENTMAX H
VENTMIN M to
MEDIUM
VENTMAX M
VENTMIN L to
LOW
VENTMAX L
VENTMIN L to
LOW
Full Open
VENTMIN H to
HIGH
Full Open
UNOCCUPIED
Closed
Closed
Closed
Closed
Closed
Closed
Closed to
Full Open
Closed to
Full Open
Closed
Closed
Closed
Closed
Closed
Closed
Closed to
Full Open
Closed to
Full Open
Closed
Closed
Closed
Closed
Closed
Closed
Closed to
Full Open
Closed to
Full Open