3. Installing the CCL002Z

Install the CC-Link communication option to VF-S11 as follows.
(1) Turn off the input power of VF-S11 and wait for at least 10 minutes and then check that
(2) Open the VF-S11 front cover, remove the terminal board fixing screw and take off the
(3) Perform wiring an inverter before installing CC-Link communication option.
(4) Please attach the insulating sheet in VF-S11.
(5) Install the CC-Link communication option over the insulating sheet and secure it with
(6) Stick the cabling label for CC-Link communication option on the standard cabling label
N.B.: To install or remove the terminal board, make it slide in or out in parallel with board.
Cabling label position
Example
VF-S11 Standard terminal board
the CHARGE lamp on VF-S11 is no longer lit.
VF-S11 standard terminal board.
(Be careful not to lose the terminal board fixing screw when removed since it may be used
again.)
(Fix to the terminal board fixing screw hole and PWB catch pin.)
the board fixing screw (tightening torque of M3 tapping screw: 0.7 to 0.8Nm).
stuck on the reverse side of the VF-S11 front cover. And stick the CC-Link
communication option
type form label
cover slits on the VF-S11 enclosure.)
VF-S11 unit (Under 3.7kW)
Insulating sheet (attached)
(It is not necessary to
cover the 5.5 to 15kW
model with an insulating
sheet.)
near the standard nameplate. (Be careful not to
DA DB DG SLD FG
CC-Link communication
option (CCL002Z)
- 8 -
E6581422③
Board catching pin
Terminal board fixing screw
(M3 screw tightening torque: 0.7 to 0.8Nm)
Board fixing screw hole
Type form label(attached)
Stick the CCL002Z type form label like
bellow figure.
CCL002Z
VF-S11 nameplate
CC-Link terminal label(attached)
Stick the label to the CC-Link terminal.
DA DB DG SLD FG