Quick Start Guide
4

Set the switches

The Rosemount 3144P Transmitter comes with hardware switches to
configure alarms and lock the device. Use the following procedures to set
the switches.
WARNING
Enclosure
Enclosure covers must be fully engaged to meet explosion-proof
requirements.
4.1
Set the switches with an LCD display
Procedure
1. Set the loop to manual (if applicable) and disconnect the power.
2. Remove the electronics housing cover.
3. Unscrew the LCD display screws and gently slide the meter straight
off.
4. Set the alarm and security switches to the desired position.
5. Gently slide the LCD display back into place.
6. Replace and tighten the LCD display screws to secure the LCD
display.
7. Reattach housing cover.
8. Apply power and set the loop to automatic control.
4.2
Set the switches without an LCD display
Procedure
1. Set the loop to manual (if applicable) and disconnect the power.
2. Remove the electronics housing cover.
3. Set the alarm and security switches to the desired position.
4. Reattach housing cover.
5. Apply power and set the loop to automatic control.
10
March 2021
Rosemount 3144P