Push battery 4 into position. Using a 7/16 in. nut driver, re-install the battery retention
15
bracket and secure with the 2 bolts removed in Step 1. Torque to 85 in-lb.

Connecting AC Power

WARNING
Ground cabinet per "Grounding" Section (page 38) prior to connecting AC power.
Tools and Materials Required
Standard tools and any tools to seal conduit
3/4-in. conduit for routing cables to the cabinet
3/4 NPT conduit fitting
(2) 2 x 12AWG wire nuts
(1) 3 x 12AWG wire nut
Seals, gaskets, or fittings rated at NEMA 4 or IP65 for the conduit ports