3.2.13 P6---Overheating protection on Cooling mode

P6 Overheating protection on Cooling mode

On Cooling or Dry mode, when ODU condenser coil temperature OPT≥144˚F, Main PCB will switch off
Switch on unit
after minutes
Display P5
3.2.12 P5---Sub-cooling protection on Cooling/Dry mode
On Cooling or Dry mode, when IDU evaporator coil temperature IPT<2 F continuously for 3 min after
compressor start up for 6 min, CPU will switch off outdoor unit and show P5 failure code.
temperature
environment
mode under low
Note: Cooling
rotate freely?
Can fan blade
blocked?
IDU air inlet
easily have P5
No
protection
Normal
Display P5
Yes
Air filter dirty?
fan blade
Check and repair
No
No
P5 disappear?
P5 disappear?
P5 disappear?
No
No
Yes
Yes
Yes
No
Clean
Clean filter
Yes
No
Yes
Yes
Sensor IPT
protection
Replace sensor
Yes
works too slow
abnormal?
Replace Display PCB
Fan motor
or stopped
End
Fan motor
No
No
Yes
No
Yes
Replace motor
defect?
42
outdoor unit and show P6 failure code.
Display
Outdoor
motor
normal?
Sensor loosing
from connector?
The sensor open
or short circuit?
Replace OPT sensor
No
P6 disappear?
Replace Main PCB
37
TROUBLESHOOTING
P6
No
fan
works
Yes
Yes
No
Yes
Yes
End
Yes
Fan motor
broken?
No
Yes
Re-connect sensor
Replace fan motor
No
P6 disappear?
No
P6 disappear?
Yes