6 Related Parameters

6
Related Parameters
The parameters outlined in the following sections are used to set up the unit for operation
with the option. Set parameters as needed. Parameter setting methods can be found in the
drive unit Instruction Manual.
Parameter Table
No.
(Addr.
Name
Hex)
F4-01
Terminal V1 Monitor Selection
(391)
F4-02
Terminal V1 Monitor Gain
(392)
F4-03
Terminal V2 Monitor Selection
(393)
F4-04
Terminal V2 Monitor Gain
(394)
F4-05
Terminal V1 Monitor Bias
(395)
F4-06
Terminal V2 Monitor Bias
(396)
F4-07
Terminal V1 Signal Level
(397)
F4-08
Terminal V2 Signal Level
(398)
<1> The unit outputs voltage while this parameter is being adjusted. Voltage levels can be adjusted to match the
specifications of an external meter.
22
Table 5 Related Parameters
Sets the monitor signal for output from
terminal V1. Set this parameter to the last
three digits of the desired U- monitor.
Some U parameters are available only in
certain control modes.
For example, enter "103" for U1-03.
Sets the gain for voltage output via terminal
V1, where 100% equals 10 V output.
Terminal output voltage is limited to 10 V.
Sets the monitor signal for output from
terminal V2. Set this parameter to the last
three digits of the desired U- monitor.
Some U parameters are available only in
certain control modes.
For example, enter "103" for U1-03.
Sets the gain for voltage output via terminal
V2, where 100% equals 10 V output.
Terminal output voltage is limited to 10 V.
<1>
Sets the amount of bias added to the voltage
output via terminal V1.
Sets the amount of bias added to the voltage
output via terminal V2.
Sets the voltage level for the analog output.
0: 0 to +10 Vdc
1: -10 to +10 Vdc
YASKAWA ELECTRIC TOBP C730600 40E 1000-Series Option AO-A3 Installation Manual
Description
<1>
<1>
Values
Default when installed
to drive: 102 (output
frequency)
Default when installed
to energy-saving unit:
000 (reserved)
Range: 000 to 999
Default: 100.0%
Min: -999.9
Max: 999.9
Default when installed
to drive: 103 (output
voltage)
Default when installed
to energy-saving unit:
000 (reserved)
Range: 000 to 999
Default: 50.0%
Min: -999.9
Max: 999.9
Default: 0.0%
Min: -999.9
Max: 999.9
Default: 0.0%
Min: -999.9
Max: 999.9
Default: 0
Range: 0, 1
Default: 0
Range: 0, 1