Model RSV-1 Residential Shut-Off Valve,
Dual-Purpose Water Supply,
Domestic and Fire Sprinkler System
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Scan the QR code or enter the URL
in a web browser to access the most
up-to-date electronic version of this
document. Data rates may apply.
docs.jci.com/tycofire/tfp982
General
Description
The TYCO Model RSV-1 Residen-
tial Shut-Off Valves are intended for
use in dual-purpose residential water
supply piping that serves both domes-
tic and residential fire protection sprin-
kler system needs. The 1 Inch (DN25)
Valve is intended for NFPA 13D system
needs, whereas the 2 Inch (DN50) Valve
is intended for systems designed in
accordance with either NFPA 13, 13D,
or 13R.
When a fire sprinkler operates, the
Model RSV-1 Residential Shut-Off
Valve automatically diverts the avail-
able water supply to the fire sprin-
kler system. Consequently, when the
Model RSV-1 Valve is utilized, the
system designer does not need to
add the domestic flow demand to the
fire sprinkler system flow demand, as
would otherwise be required by NFPA
13D or 13R.
Page 1 of 6
Consider use of the Model RSV-1 Res-
idential Shut-Off Valve when either
the water supply cannot adequately
provide for both the domestic design
demand and the fire sprinkler flow
demand, or it is necessary to increase
the effectiveness of the fire sprinkler
system by automatically diverting the
domestic flow.
The Model RSV-1 Residential Shut-
Off Valve maximizes the effective use
of an existing water supply. There-
fore, in areas with limited water sup-
plies, it may eliminate the need to add
costly pumps, pressurized reservoirs,
or electrically operated domestic shut-
off valves. The Model RSV-1 Valve has
a built-in check valve in the fire sprin-
kler system outlet that eliminates the
need for a separate check valve. Also,
the Model RSV-1 Valve automatically
resets, thereby eliminating the need for
valve disassembly after a fire sprinkler
system test or operation.
NOTICE
The Model RSV-1 Residential Shut-
Off Valves described herein must be
installed and maintained in compliance
with this document, as well as with the
applicable standards of the National
Fire Protection Association, in addi-
tion to the standards of any authorities
having jurisdiction. Failure to do so may
impair the integrity of this device.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
AUGUST 2022
Worldwide
www.tyco-fire.com
Contacts
Technical
Data
Approvals
UL and C-UL Listed
Certified to all requirements of
NSF/ANSI 61, Annex G and NSF/ANSI 372
Note: The 1 Inch (DN25) Model RSV-1
Residential Shut-Off Valve is suitable
for use in water supply arrangements
for residential fire sprinkler systems
designed per NFPA 13D.
Note: The 2 Inch (DN50) Model RSV-1
Residential Shut-Off Valve is suitable
for use in water supply arrangements
for residential fire sprinkler systems
designed per NFPA 13, 13D, or 13R.
Maximum Pressure
175 psi (12,1 bar)
Weight
1 Inch (DN25): 11 lbs. (5 kg)
2 Inch (DN50): 29 lbs. (11 kg)
Pressure Loss
Refer to Graphs A and B
Patents
2 Inch (DN50) Model RSV-1 Valve Patent
Pending
TFP982

Advertisement

loading

Summary of Contents for Johnson Controls Tyco RSV-1

  • Page 1 Worldwide www.tyco-fire.com Contacts Model RSV-1 Residential Shut-Off Valve, Dual-Purpose Water Supply, Domestic and Fire Sprinkler System Consider use of the Model RSV-1 Res- IMPORTANT idential Shut-Off Valve when either Refer to Technical Data Sheet the water supply cannot adequately TFP2300 for warnings pertaining to provide for both the domestic design regulatory and health information.
  • Page 2: Operating Principles

    TFP982 Page 2 of 6 Physical Characteristics FIRE SPRINKLER AUTOMATIC FIRE SPRINKLERS 1 Inch (DN25) Valve SYSTEM PRESSURE Body ..... . Stainless Steel GAUGE Top and Bottom Cover .
  • Page 3 TFP982 Page 3 of 6 The momentary opening and re-clos- 3-5/8" DIA. FIRE ing of the Piston Assembly at the Fire (92,1 mm) SPRINKLER Components: Sprinkler Line Seal traps a portion PORT, 1" NPT of the pressure increase within the Body fire sprinkler system.
  • Page 4: Installation

    TFP982 Page 4 of 6 FLOW RATE IN LITERS PER MINUTE (LPM) FLOW RATE IN LITERS PER MINUTE (LPM) (1 GPM = 3,785 LPM) (1 GPM = 3,785 LPM) 60 80 10.0 0,40 0,60 0,30 0,50 0,20 0,40 0,30 0,10 0,08 0,20 0,06...
  • Page 5 TFP982 Page 5 of 6 FIRE FIRE TO FIRE SPRINKLER PISTON SPRINKLER PISTON SPRINKLERS PORT ASSEMBLY ASSEMBLY PORT FIRE FIRE FIRE SPRINKLER SPRINKLER SPRINKLER SEAT SEAT FLOW PASSAGE DOMESTIC PORT DOMESTIC DOMESTIC DOMESTIC PORT FLOW INTERNAL PASSAGE BY-PASS RESTRICTION DOMESTIC SEAT DOMESTIC SUPPLY...
  • Page 6: Care And Maintenance

    1467 Elmwood Avenue, Cranston, RI 02910 | Telephone +1-401-781-8220 © 2022 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice. NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;...