2.2 ELECTRICAL CONNECTION

ELECTRICAL
ELECTRICAL
ENTRY POINT
ENTRY POINT
TRANSPORT BLOCK
POSITION OF
22.00
22.00
40.00
40.00
ELECTRIC BOX
CAUTION!
REMOVE COMPRESSOR TRANSPORT BLOCK BEFORE RUNNING MACHINE
DH66 DEHUMIDIFIER SHOWN
POSITIONS OF KNOCKOUTS FOR ELECTRICAL CONNECTION
The electrical connection should be carried out by an authorised electrician, paying special
attention to the latest IEE regulations. In any case, the mains power supply should be fitted with
a 30mA/30ms protection switch. The cable access position can be selected by the customer
from the positions shown above. Once the desired knockout has been removed a cable gland
(supplied in package) can be fitted to neaten off the hole.
The electric box is situated under the compressor cover which will need to be removed.
The connections are made to the terminal box on the outside of the electric box in the bottom
right hand corner of the dehumidifier.
The machine should be installed in accordance with EMC2004/108/EC.
FAN MODE SWITCH
A fan mode switch is positioned on the electric box with the following modes:
Fan continuous - continuous operation of the fan.
Fan cycle - the fan will be switched on and off automatically by the humidistat.
The mode "fan cycle" helps, especially with a covered swimming pool, to save energy:
(but in this mode larger humidity swings may be experienced).
After connecting the electrical supply, the compressor cover and machine cover need to be
installed in the manner shown on page 5.
The dehumidifier is now ready to operate.
Attention. The dehumidifier should not be switched on without it's covers in place. Operation
without a cover causes poor airflow. Due to safety features the unit will switch off after a short
period of time.