Bryant Legacy 569J 16-28 Installation Instructions Manual page 22

Table of Contents

Advertisement

gauge to the service port on the liquid line service valve.
Mount the temperature sensing device on the liquid line close
to the liquid line service valve, and insulate it so that outdoor
ambient temperature does not affect the reading. Indoor airflow
must be within the unit's normal operating range. Operate the
unit for a minimum of 15 minutes. Ensure that pressure and
temperature readings have stabilized. Plot the liquid pressure
and temperature on chart and add or reduce the charge to meet
the curve. see Table 15. Adjust the charge to conform with the
charging chart, using the liquid pressure and temperature to
read the chart.
Table 15 — Using Plotted Operating Point
IF PLOTTED OPERATING
CONDITION IS
BELOW the curve
ABOVE the curve
569J*25A/B CHECK COMPRESSOR OIL LEVEL
After adjusting the refrigerant charge, allow the unit to run ful-
ly loaded for 20 minutes. Stop the compressors and check the
oil level. Oil level should be 1/3 to 1/2 up on the sight glass
(see Fig. 23).
60
54
48
42
36
30
24
18
12
-6
ADJUST CHARGE BY
REDUCE charge
ADD charge
15 Ton Charging Chart R-410A Refrigerant
140
120
Add Charge if
Above the Curve
100
80
60
6
40
0
20
50
100
150
200
350
700
1050 1400 1750 2100 2450 2800 3150 3500 3850
Pressure at Liquid Valve (PSIG / kPa)
Fig. 24 — 569J*16A/B Charging Chart
1/2 (MAX)
1/3 (MIN)
Fig. 23 — Recommended Oil Level — 569J*25A/B
Add oil only if necessary to bring the oil into view in the sight
glass. If oil is added, run the circuit for an additional 10 min-
utes, then stop and check oil level. If the level remains low,
check the piping system for proper design for oil return; also,
check the system for leaks. If checking the oil level with unit
running in part load, let unit run one hour, then run at full load
for 10 minutes. If oil does not return to acceptable sight glass
levels, check for correct suction piping and line sizing.
FINAL CHECKS
Ensure that all safety controls are operating, control panel cov-
ers are on, and the service panels are in place.
Remove Charge if
Below the Curve
250
300
350
400
450
22
500
550
600
38AU501082
C

Advertisement

Table of Contents
loading

Table of Contents