Bradford White TTW ULG2PV50H565N19 Installation And Operation Instruction Manual

Bradford White TTW ULG2PV50H565N19 Installation And Operation Instruction Manual

Power vent gas water heater

Advertisement

Quick Links

A Spanish language version of these instructions is available by contacting the
company listed on the rating plate.
La version espanola de estas instrucciones se puede obtener al escribirle a la
fabrica cuyo nombre aparece en la placa de especificaciones.
WARNING:
followed exactly, a fire or explosion may result causing
property damage, personal injury, or death.
Do not store or use gasoline or other flammable,
combustible, or corrosive vapors and liquids in the
vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not use any
phone in your building.
Immediately call your gas supplier from a neighbor's
phone. Follow the gas supplier's instructions.
If you cannot reach your gas supplier, call the fire
department.
Installation and service must be performed by a qualified
installer, service agency or the gas supplier.
For your family's comfort, safety and convenience we
recommend this water heater be installed and serviced by a
plumbing professional.
POWER VENT GAS WATER HEATER
INSTALLATION AND OPERATION
INSTRUCTION MANUAL
If the information in these instructions is not
FOR YOUR SAFETY
238-51000-00D REV 5/18

Advertisement

Table of Contents
loading

Summary of Contents for Bradford White TTW ULG2PV50H565N19

  • Page 1 POWER VENT GAS WATER HEATER A Spanish language version of these instructions is available by contacting the company listed on the rating plate. La version espanola de estas instrucciones se puede obtener al escribirle a la fabrica cuyo nombre aparece en la placa de especificaciones. INSTALLATION AND OPERATION INSTRUCTION MANUAL WARNING:...
  • Page 2 CONGRATULATIONS! You have just purchased one of the finest water heaters on the market today! This installation, operation and instruction manual will explain in detail the installation and maintenance of your new Power Vent Gas Water Heater. We strongly recommend that you contact a plumbing professional for the installation of this water heater.
  • Page 3: Table Of Contents

    TABLE OF CONTENTS page GENERAL INFORMATION ..............INSTALLATION................... Locating The Water Heater ............Minimum Clearances ..............Venting ..................Specifications for 48 Gal (181.6 L) ..............Vent Pipe Preparation and Joining ..........Combustion Air Supply ............... Water Connections ..............Gas Connections ................Electrical Connections ..............
  • Page 4: General Information

    GENERAL INFORMATION This gas-fired water heater’s design is certified by CSA International under the American National Standard Z21.10.1 and CSA 4.1-M, most current editions at the time of manufacture. This is a category III water heater. This water heater must be installed in accordance with local codes or, in the absence of local codes, the National Fuel Gas Code, ANSI Z223.1-Latest Edition) and/or in Canada CAN/CGA B149 Installation Codes (Latest Editions).
  • Page 5: Installation

    General Information continued- Make sure that you check the rating plate and combination gas control on the water heater to be certain that the type of gas being supplied corresponds with the marking on the rating plate and combination gas control. A sacrificial anode(s) is used to extend tank life.
  • Page 6 Installation (Locating The Water Heater) continued- The location of this water heater is of the utmost importance. Before installing this water heater, read the installation section of these instructions. After reading these installation and operating instructions, select a location for the water heater where the floor is level and is easily accessible to gas and water supply lines.
  • Page 7 Installation (Locating The Water Heater) continued- WARNING DO NOT ATTEMPT TO LIGHT ANY GAS APPLIANCE IF YOU ARE NOT CERTAIN OF THE FOLLOWING: • Liquefied petroleum gases/propane gas and natural gas have an odorant added by the gas supplier that aids in the detection of the gas.
  • Page 8: Minimum Clearances

    Minimum Clearances WARNING Failure to adhere to these installation and operating instructions may create a hazard to life and property and will nullify the warranty. This installation must allow access to the front of the water heater and adequate clearance must be provided for servicing and operating this water heater. The water heater may be installed on either a combustible or non-combustible floor.
  • Page 9 Venting continued- Canadian US Installations Installations Clearance above grade, veranda, 12 inches 12 inches porch, deck or balcony (30 cm) (30 cm) Clearance to window or door that may 12 inches 4 feet (1.2 m) below or be opened (30 cm) to the side of opening;...
  • Page 10 Venting continued- Vent pipes serving power vented appliances are classified by building codes as “vent connectors”. Required clearances from combustible materials must be provided in accordance with information in this manual under LOCATION OF WATER HEATER and CLEARANCES, and with National Fuel Gas Code and local codes.
  • Page 11 Venting continued- Approved Venting Materials For installations in the US For installations in CANADA • ULC S636 approved PVC for only • PVC DWV (ASTM D-2665) flue gas venting rated Class II, 65°C • PVC Sch. 40, 80, 120 (ASTM- •...
  • Page 12: Gal (181.6 L)

    Venting continued- In order to prevent condensate from draining back into the blow er (vertical or horizontal runs), an optional condensate kit is available as a service part (Condensate kit, p/n 239-45875-00). A factory supplied exhaust adapter w ith drain outlet mounts directly to the blow er outlet and is secured w ith tw o hose clamps, one to the blow er and the ot her to the vent pipe.
  • Page 13 Venting continued- TABLE 2 -VENT CONNECTOR LENGTHS FOR 4’’ (10.2 cm) DIAMETER VENT PIPE Terminating Maximum straight # of 90° Length ft (m) straight Elbows (excl. Length vent term.) 48 gal. ft (m) 175 (53.3) Through the Wall 10 (3.1) 170 (51.8) Through the Wall 10 (3.1)
  • Page 14 Venting continued- THROUGH THE WALL VENTING: (HORIZONTAL VENTING) Cut a 3 1/2 in. (8.9 cm) diameter hole in the w all at the point w here the vent connector is going to pass through the w all. Use the proper cement to secure the 90°...
  • Page 15 Venting continued- THROUGH THE ROOF VENTING: (VERTICAL VENTING) Cut the necessary holes through the roof and ceiling and install the vent connector as show n in Figure 4. Make sure that the installation meets the local codes and/or The National Fuel Gas Code ANSI Z223.1 (Latest Edition) or CGA/CAN B149 Installation Code (latest edition).
  • Page 16 Venting continued- THROUGH THE WALL VENTING WITH LOW GROUND CLEARANCE: When venting cannot exit through the wall at a height greater than or equal to 12” (30.5 cm) above the ground, or anticipated snow level, the installation must be modified as shown below (see Figure 5). Refer to Table 3 for maximum venting lengths using 3”...
  • Page 17 Venting continued- TABLE 3 3” (7.6 cm) VENT CONNECTOR LENGTHS FROM INSIDE WALL FOR LOW GROUND CLEARANCE INSTALLATIONS Terminating # of Max Straight Elbows Length ft (m) straight Length 48 gal. ft (m) 30 (9.1) 5 (1.5) (2) 90° Elbows with (1) 90° Elbow 25 (7.6) 5 (1.5) (2) 90°...
  • Page 18: Vent Pipe Preparation And Joining

    Vent Pipe Preparation and Joining Most failures in vent systems result from improper preparation and joining of pipe and fittings. The guidelines below must be follow ed w hen installing the venting system. If you have any question about the application or installation of the venting system, contact the vent pipe manufacturer, supplier, or your plumbing professional.
  • Page 19 Vent Pipe Preparation and Joining continued- d) Cementing must be done quickly to avoid over-drying before joining. Apply one coat to the outside end of the pipe at a w idth slightly greater than the depth of the socket. ii) Apply a coat around the inside of the fitting socket. iii) Apply a second coat around the end of the pipe.
  • Page 20: Combustion Air Supply

    Combustion Air Supply WARNING Liquefied petroleum gases/propane gases are heavier than air and will remain at floor level if there is a leak. Basements, crawl spaces, closets and areas below ground level will serve as pockets for accumulation of leaking gas. Before lighting, smell all around the appliance area for gas. Be sure to smell next to the floor.
  • Page 21 Installation (Combustion Air Supply) continued- All Air From Inside the Building: The confined space must be provided with two permanent openings communicating directly with an additional room(s) of sufficient volume so that the combined volume of all spaces meets the criteria for an unconfined space.
  • Page 22: Water Connections

    Water Connections NOTE: BEFORE PROCEEDING WITH THE INSTALLATION, CLOSE THE MAIN WATER SUPPLY VALVE. After shutting off the main water supply, open a faucet to relieve the water line pressure to prevent any water from leaking out of the pipes while making the water connections to the water heater.
  • Page 23 Water Connections continued- WARNING For protection against excessive temperatures and pressure, install temperature and pressure protective equipment required by local codes, but not less than a combination temperature and pressure relief valve certified by a nationally recognized testing laboratory that maintains periodic inspection of production of listed equipment or materials as meeting the requirements of the Standard for Relief Valves and Automatic Gas Shutoff Devices for Hot Water Supply Systems, ANS...
  • Page 24 Water Connections continued- WARNING Hydrogen gas can be produced in an operating water heater that has not had water drawn from the tank for a long period of time (generally two weeks or more). Hydrogen gas is extremely flammable. To prevent the possibility of injury under these conditions, we recommend the hot water faucet to be open for several minutes at the kitchen sink before you use any electrical appliance which is connected to the hot water system.
  • Page 25: Gas Connections

    Gas Connections WARNING Prior to connecting the gas supply line to a gas fired water heater, ensure that the gas supply line does not have moisture/water or dirt/scale inside the gas line. Commonly this check is done at the lowest point in the gas distribution system prior to gas burning appliances.
  • Page 26: Electrical Connections

    While checking for leaks care must be taken to prevent solution from contacting the electrical connections at the control. If electrical connect ions at the control become w et, they must be thoroughly dried before attempting to operate the w ater heater. Electrical Connections All electrical w iring and connections must be in accordance w ith the National Electric Code ANSI/NFPA No.
  • Page 27: Wiring Diagram

    Wiring Diagram Figure 6...
  • Page 28: General Operation

    GENERAL OPERATION WARNING Water heaters are heat producing appliances. To avoid damage or injury there must be no materials stored against the water heater or vent-air intake system, and proper care must be taken to avoid unnecessary contact (especially by children) with the water heater and vent-air intake system.
  • Page 29: Lighting And Shutdown Instructions

    Lighting and Shutdown instructions...
  • Page 30: Thermostat Adjustment

    Thermostat Adjustment The thermostat dial is adjusted to its lowest setting when shipped from the factory. When adjusting the thermostat, it should be remembered that lower temperature settings are more energy efficient. To adjust the thermostat turn the dial clockwise until the minimum acceptable temperature is set. It is suggested that the starting point setting not exceed the 120°F (49°C) or “HOT”...
  • Page 31: Burner Flame Check

    Burner Flame Check Steel Burner: These models are equipped with self-adjusting air mixture and do not have an adjustable air shutter (See Figure 8). At periodic intervals a visual check of the main burner and pilot flames should be made to determine if they are burning properly.
  • Page 32: Maintenance

    MAINTENANCE WARNING Water heaters are heat producing appliances. To avoid damage or injury there must be no materials stored against the water heater or vent-air intake system, and proper care must be taken to avoid unnecessary contact (especially by children) with the water heater and vent-air intake system.
  • Page 33 Maintenance continued- 5. Annually remove the inner door and main burner assembly to clean orifices and related parts of any dirt or other foreign material. Inspect the burner ports for obstructions or debris and clean with a wire brush as needed. Wire brush and/or vacuum clean the combustion chamber as needed to remove scale deposits and debris.
  • Page 34 Maintenance continued- WARNING When lifting lever of the combination temperature and pressure relief valve, hot water will be released under pressure. Be careful that any released water does not result in bodily injury or property damage. WARNING Do not run out of propane gas. Damage to the water heater may occur. 6.
  • Page 35 Maintenance continued- CAUTION FOR YOUR SAFETY, DO NOT ATTEMPT REPAIR OF COMBINATION GAS CONTROL, BURNERS OR GAS PIPING. REFER REPAIRS TO A QUALIFIED SERVICE TECHNICIAN. Contact your supplier or plumbing professional for replacement parts or contact the company at the address given on the rating plate of the water heater. Provide the part name, model and serial numbers of the water heater when ordering parts.
  • Page 36: Troubleshooting

    TROUBLESHOOTING LED Status Control Status Probable Cause None (LED not on or Electrical power not Control power switch in “OFF” position.Supply flashing) present. voltage interuppted. Stand-by mode, One short flash every Thermostat is Temperature demand is satisfied (no call for heat). four seconds satisfied (no faults).
  • Page 37 Troubleshooting continued- LED Status Control Status Probable Cause 1. Pressure switch tubing kinked or blocked. 2. Vent blockage or improper vent Pressure switch or configuration. blower temperature Six flashes-two 3. Vent termination being affected by windy switch opened during flashes, three second conditions.
  • Page 38 Control Sequence of Operation Start up Sequence Upon pow ering up, the control checks for the presence of the vapor sensor, if the resistance is in the expected range the control w ill begin normal operation after 5 to 8 seconds. Normal Heating Sequence The thermostat senses a need for heat.
  • Page 39: Parts List Drawing

    PARTS LIST DRAWING PARTS LIST PART NAME AND DESCRIPTION 1. Blow er Assembly 14. T&P Relief Valve 2. Temp. Sw itch 15. Pilot Assembly 3. Pressure Sw itch 16. Adapter 4. Flue Baffle 17. Main Burner Orifice 5. Honeyw ell Gas Control Valve 18.
  • Page 40: Space Heating

    THE FOLLOWING INSTRUCTIONS ARE FOR INSTALLATION OF: GAS WATER HEATERS SUITABLE FOR WATER (POTABLE) HEATING AND SPACE HEATING 1. All piping components connected to this water heater for space heating applications must be suitable for use with potable water. In Massachusetts, space heating piping length must not exceed 50 feet.