Viking FREEDOM VK480 Technical Data Manual page 6

Residential concealed horizontal sidewall sprinkler

Advertisement

Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.
Sprinkler
Base Part
SIN
Number
3
16116AC
VK480
Max.
Centerline of
coverage
sprinkler to
area
ceiling
4
W x L (m x m)
(mm)
3.7 x 3.7
4.3 x 4.3
110 to 162
4.9 x 4.9
4.9 x 5.5
3.7 x 3.7
4.3 x 4.3
162 to 314
4.9 x 4.9
4.9 x 5.5
Not for North American markets. The VK480 is a vented style concealed sprinkler. Do not install embedded in concrete ceilings.
1.
Accepted Cover Plate Finishes are: Polished Chrome, Brushed Chrome, Bright Brass, Antique Brass, Brushed Brass, Brushed Copper, Painted White, Painted Ivory, or
2.
Painted Black. Other paint colours are available on request with the same listings as the standard finish colours. Listings and approvals apply for any paint manufacturer.
Contact Viking for additional information. Custom colours are indicated on a label inside the cover assembly. Refer to Figure 1.
Part number shown is the base part number. For complete part number, contact Viking.
3.
For areas of coverage smaller than shown, use the "Flow" and "Pressure" for the next larger area listed. Flows and pressures listed are per sprinkler. The distance from
4.
sprinklers to walls shall not exceed one-half the sprinkler spacing indicated for the minimum "Flow" and "Pressure" used. For detailed guidance on obstructions please
refer to the relevant EN16925, NFPA13, 13R or 13D design and installation standards. The minimum flow for each sprinkler shall be selected such that both the actual
width and length dimensions are equal to or less than those given in the table above.
Minimum LPCB approved flow and pressure for each room size.
5.
Flow and pressure required to achieve nominal density, or minimum approved flow and pressure if higher.
6.
The nominal density is that used for design purposes and required by the installation standard. As a proportion of the flow is required to wet the walls the actual density
7.
on the floor will be lower than nominal. Product testing and approvals are carried out at the minimum values given above and so design should be based on the values
given above and does not need to be adjusted to take account of wall-wetting.
Form No. F_121609
Rev 01
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Approval Chart - LPCB
Viking VK480, K58 Residential Concealed HSW Sprinkler
For systems designed according to EN16925 including UK National Annex and BS9251
74°C sprinkler with 57°C coverplate
Thread
½"
Minimum design
criteria
5
Flow
Pressure
(L/min)
(bar)
41.7
49.3
60.6
64.4
45.5
53
60.6
68.1
September 7, 2022
TECHNICAL DATA
Nominal K-Factor
(metric)
57.7
Nominal
6,7
2.1mm/min
Flow
Pressure
(L/min)
(bar)
0.5
41.7
0.5
0.7
49.3
0.7
1.1
60.6
1.1
1.2
64.4
1.2
0.6
45.5
0.6
0.8
53.0
0.8
1.1
60.6
1.1
1.4
68.1
1.4
Footnotes
FREEDOM
®
CONCEALED HORIZONTAL
SIDEWALL SPRINKLER VK480
(K4.0)
1
2
Maximum Working
Pressure (bar)
12.0
Nominal
6,7
2.8mm/min
Flow
Pressure
(L/min)
(bar)
41.7
0.5
51.8
0.8
67.2
1.3
67.2
1.3
45.5
0.6
53.0
0.8
67.2
1.3
68.1
1.4
Page 6 of 9
RESIDENTIAL
Minimum Spacing (m)
2.4
Nominal
6,7
4.0mm/min
Flow
Pressure
(L/min)
(bar)
54.8
0.9
74.0
1.6
96.0
2.7
96.0
2.7
54.8
0.9
74.0
1.6
96.0
2.7
96.0
2.7