Viking VK572 Technical Data Manual

Viking VK572 Technical Data Manual

Ec/qrec ordinary hazard pendent sprinkler

Advertisement

Quick Links

Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
1. DESCRIPTION
Viking Standard/Quick Response Extended Coverage Ordinary Hazard (ECOH)
Pendent Sprinkler VK572 is a thermosensitive glass bulb spray sprinkler with a
14.0 (202 metric
) nominal K-Factor. The sprinkler produces the flows required to
*
meet Ordinary Hazard density requirements at lower pressures than 8.0 or 11.2
(115.2 or 161.4 metric*) K-Factor sprinklers. The glass bulb operating element and
special deflector characteristics meet the challenges of quick response extended
coverage standards. Viking EC/QREC Ordinary Hazard Sprinklers are available in
various finishes and temperature ratings to meet design requirements. The spe-
cial Polyester coatings can be used in decorative applications where colors are
desired. In addition, the ENT coating has been investigated for installation in cor-
rosive environments and is listed as indicated in the Approval Charts. The Viking
VK572 Sprinkler may be ordered and/or used as an open sprinkler (glass bulb and
pip-cap assembly removed) on deluge systems. Refer to
the next page.
2. LISTINGS AND APPROVALS
cULus Listed: Category VNIV
FM Approved: Class 2022
NYC Approved: MEA 89-92-E, Volume 38
Refer to Approval Chart 1 and Design Criteria for cULus Listing requirements and refer to Approval Chart 2 and Design
Criteria for FM Approval requirements that must be followed.
3. TECHNICAL DATA
Specifications:
Available since 2004.
Minimum Operating Pressure: Refer to the Approval Charts.
Maximum Working Pressure: 175 psi (12 bar). Factory tested hydrostatically to 500 psi (34.5 bar).
Thread size: 3/4" (20 mm) NPT
Nominal K-Factor: 14.0 U.S. (202 metric
* Metric K-factor measurement shown is in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
Glass-bulb fluid temperature rated to -65 °F (-55 °C)
Overall Length: 2-7/16" (62 mm)
Material Standards:
Sprinkler Frame: Brass UNS-C84400
Deflector: Phosphor Bronze UNS-C51000
Bulb: Glass, nominal 3 mm diameter
Pip Cap: Brass UNS-C31400 or UNS-C31600
Compression Screw: Brass UNS-C36000
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape
For ENT coated Sprinklers: Belleville Spring - Exposed, Screw and Pipcap - ENT plated.
For Polyester Coated Sprinklers: Belleville Spring-Exposed
Ordering Information: (Also refer to the current Viking price list.)
Order EC/QREC Ordinary Hazard Pendent Sprinkler VK572 by first adding the appropriate suffix for the sprinkler finish and then
the appropriate suffix for the temperature rating to the sprinkler base part number.
Finish Suffix: Brass = A, Chrome = F, White Polyester = M-/W, Black Polyester = M-/B, and ENT = JN
Temperature Suffix (°F/°C): 155°/68° = B, 175°/79° = D, 200°/93° = E, and 286°/141° = G, OPEN = Z (PTFE only).
For example, sprinkler VK572 with a Brass finish and a 155 °F/68 °C temperature rating = Part No. 13722AB.
Available Finishes And Temperature Ratings: Refer to Table 1.
Form No. F_072313
19.02.21
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
)
*
Rev 19.1
Ordering Instructions
on
Replaces Form No. F_072313 Rev 18.3.P65
EC/QREC ORDINARY
HAZARD PENDENT
SPRINKLER VK572 (K14.0)
NOTE: As of May 2018 all logos have been removed from
the wrench boss.
(Removed F-1 Escutcheon.)
Page 1 of 6

Advertisement

loading

Summary of Contents for Viking VK572

  • Page 1 Ordering Information: (Also refer to the current Viking price list.) Order EC/QREC Ordinary Hazard Pendent Sprinkler VK572 by first adding the appropriate suffix for the sprinkler finish and then the appropriate suffix for the temperature rating to the sprinkler base part number.
  • Page 2: Technical Data

    The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com Accessories: (Also refer to the Viking website.) Sprinkler Wrenches: A.
  • Page 3 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES...
  • Page 4 “Minimum Water Supply Requirement” used. For Sprinkler VK572 with High Temperature 286 °F rating, UL restricts the QR listing to their use in Ordinary Hazard occupancies to the high temperature zones within a building only. VK572 quick response sprinklers with this temperature rating cannot be used throughout the property.
  • Page 5 • cULus Listing requires the spacing between Viking ECOH Pendent Sprinklers to be a minimum of 9 ft. (2.75 m) to prevent cold soldering. Viking ECOH Pendent Sprinklers are cULus Listed for use in unobstructed construction, and noncombustible obstructed construction consisting •...
  • Page 6 FM Approval Requirements: Sprinkler VK572 is FM Approved as a quick response Non-Storage extended coverage pendent sprinkler as indicated in the FM Approval Guide for use in occupancy hazard classifications HC-1, HC-2, and HC-3. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (including Data Sheet 2-0 and 3-26).
  • Page 7 Refer to the appropriate technical data page and NFPA standards for complete care, handling, installation, and maintenance instructions. For additional product and system information Viking data pages and installation instructions are available on the Viking Web site at www.vikinggroupinc.com.
  • Page 8 * Refer to the appropriate current technical data pages for complete care, handling, and installation instructions. Data pages are included with each shipment from Viking or Viking distributors. They can also be found on the Web site at www. vikinggroupinc.com.
  • Page 9 • while ceiling finish work is being completed. Use only the designated Viking recessed sprinkler wrench (refer to the appropriate sprinkler data page) to install these sprinklers. NOTE: The protective cap is • temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed.
  • Page 10 Take care not to crack the wax coating on the units. • For touching up the wax coating after installation, wax is available from Viking in bar form. Refer to Table 1 below. The coating MUST be repaired after •...
  • Page 11: Listings And Approvals

    1. DESCRIPTION Viking fire sprinklers consist of a threaded frame with a specific waterway or orifice size and a deflector for distributing water in a specified pattern. A closed or sealed sprinkler refers to a complete assembly, including the thermosensitive operating element. An open sprinkler does not use an operating element and is open at all times.
  • Page 12 TECHNICAL DATA SPRINKLER OVERVIEW The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com VERTICAL SIDEWALL (VSW) SPRINKLER: A sprinkler intended for installation near the wall and ceiling. The deflector provides a water spray pattern outward in a quarter-spherical pattern and can be installed in the upright or pendent position with the flow arrow in the direction of discharge.
  • Page 13 Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. AVAILABILITY Viking sprinklers are available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. GUARANTEE For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.