Coding in the delivered condition
Ext. Heating program changeover to heating circuit
91:0
No external heating pro-
gram changeover via
external extension
Set flow temperature in case of ext. demand
9b:0
No minimum flow temper-
ature in case of external
demand
Boiler
Coding
Coding in the delivered condition
Burner service in 100 hours
21:0
No maintenance interval
(hours run) selected
Service interval in months
23:0
No time interval for
burner service
Possible change
91:1
The external heating pro-
gram changeover affects
the heating circuit without
mixer
91:2
The external heating pro-
gram changeover affects
the heating circuit with
mixer
91:3
The external heating pro-
gram changeover affects
the heating circuit without
mixer and the heating cir-
cuit with mixer
9b:1
Set value for minimum flow
to
temperature in case of
9b:127
external demand, adjusta-
ble from 1 to 127 °C (limited
by boiler-specific parame-
ters)
Possible change
21:1
The number of hours run
to
before the burner should
21:100
be serviced is adjustable
from 100 to 10 000 h
One adjusting step ≙ 100
h
23:1
Interval adjustable from 1
to
to 24 months
23:24