5
Venting
(continued)
7. Do not install Non-listed (AGA, CGA, CSA,
ETL, or UL) vent damper or other obstruction in
vent pipe.
8. Locate Boiler as close to Chimney as possible
consistent with necessary clearances. See
Section 1: Pre-Installation.
9. Design vent system for sea level input.
10. Provide adequate ventilation of Boiler Room.
See Section 1: Pre-Installation.
11. Never pass any portion of vent system through
a circulating air duct or plenum.
!
WARNING
When an existing boiler is removed from a
common venting system, the common venting
system is likely to be too large for proper
venting of the appliances remaining connected
to it.
H. If an Existing Boiler is Removed:
At the time of removal of an existing boiler, the
following steps shall be followed with each
appliance remaining connected to the common
venting system placed in operation, while the
other appliances remaining connected to the
common venting system are not in operation:
1. Seal any unused openings in the common
venting system.
2. Visually inspect the venting system for proper
size and horizontal pitch and determine
there is no blockage or restriction, leakage,
corrosion, or other deficiencies which could
cause an unsafe condition.
3. Insofar as is practical, close all building doors
and windows and all doors between the space
in which the appliances remaining connected
to the common venting system are located and
other spaces of the building. Turn on clothes
dryers and any appliance not connected to the
common venting system. Turn on any exhaust
fans, such as range-hoods and bathroom
exhausts, so they will operate at maximum
speed. Do not operate a summer exhaust fan.
Close fireplace dampers.
4. Place in operation the appliance being
inspected. Follow the Lighting (or Operating)
Instructions. Adjust thermostat so appliance
will operate continuously.
26
8HE
Installation, Operating & Service Instructions
5. Test for spillage at the draft hood relief opening
after 5 minutes of main burner operation. Use
the flame of a match or candle, or smoke from
a cigarette, cigar or pipe.
6. After it has been determined that each
appliance remaining connected to the common
venting system properly vents when tested as
outlined above, return doors, windows, exhaust
fans, fireplace dampers and any other gas-
burning appliance to their previous condition of
use.
7. Any improper operation of the common venting
system should be corrected so the installation
conforms with the National Fuel Gas Code,
NFPA 54/ANSI Z223.1. When resizing any
portion of the common venting system, the
common venting system should be resized
to approach the minimum size as determined
using the appropriate tables in the National
Fuel Gas Code, NFPA 54/ANSI Z223.1.
Figure 5-3: Typical Vent System
111828-01 - 1/23