Carrier CDII-184R1-0CTR4 Installation & Operation Manual page 65

Inverter ducted indoor & outdoor unit
Table of Contents

Advertisement

11.3.1.4 FILTER DRIER
1. Whenever compressor is changed from system replace filter drier.
2. Turn off unit power supply.
3. Unscrew filter drier clamp.
4. Unbolted filter drier & replace it.
5. Reassemble unit.
11.3.1.5 REFRIGERANT SYSTEM
Leak testing
Quarterly check joints at valves / flare connections for leaks. In case of any leaks, repair leak and
evacuate and dehydrate unit before charging.
Refrigerant charge
Charging with unit off and Evacuated
Weight in specified charge open liquid line service valve (ensure the cylinder is upside down to make
sure only liquid is charge thru liquid line). Separate the cylinder from liquid valve along with hose.
Start unit and allow it to run several minutes fully loaded. Check for a clear liquid then Be sure, clear
condition is liquid and not vapor.
Charging with unit running
If charge is to be added while unit is operating, it is necessary to have all fans, blower and compressor
operating. Charge circuit until suction gauge shows 120 to 130 psig or liquid gauge shows 400 to 430
psig. Final adjustment may be done after stabilization of temperatures.
Do not overcharge, and never charge liquid into low-pressure (suction) side of system. If system is
charged through suction side, liquid refrigerant goes into compressor and gets mixed up with
compressor oil. When compressor is on, this liquid refrigerant mixed with compressor oil leads to
compressor oil washout and further results in compressor failure.
Observation
No display appearance on
remotes cordless.
All symbols appear on press
of any Button on remote
cordless.
Cordless Remote is working
properly,
But Machine is not starting
when power supply turns ON
or gives Alarm.
Table_5: Troubleshooting Guide
Possible causes
No batteries. Batteries are
exhausted.
Batteries are placed with
wrong polarity. Alarm
continuously
Remote software malfunction.
Cordless Remote is not
correctly directed towards
corded remote Obstacle
between Cordless remote &
machine.
Cordless Remote is exposed to
intense sunlight.
There is electromagnetic ray
interference.
Corded remote is
disconnected.
65
To do
Check Battery cells of AAA size,
1.5V & place them with correct
polarity in cordless remote.
Call Carrier Service helpline.
Re insert batteries and check.
If still problem, persist Call Carrier
Service helpline
Direct the remote towards the unit
and then press ON/OFF Button of
remote, alarm must come.
Remove any kind of obstacle in
between remote and corded
remote.
Draw down the window shades or
curtains. Avoid direct sunlight.
Remove the mobile phones or any
other electronic device near the
remote. Turn OFF the unit and

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents