Performance Data - 2.5 Ton - York LX Series Technical Manual

Hide thumbs Also See for LX Series:
Table of Contents

Advertisement

5753883-BTG-C-0221

PERFORMANCE DATA - 2.5 TON

CONDENSER-ONLY DATA (OUTDOOR UNIT)
SATURATED SUCTION
@ COMPRESSOR
MODEL
T (°F)
35
40
TW4B3022S
45
50
55
Notes:
1. For Outdoor Unit (Condenser) performance only. Data does not include the effects of air handler power or heat.
2. Performance based on 15°F subcooling and 15°F superheat at the Outdoor Unit base valves.
a. Increase capacity by 1% for each 2°F increase in subcooling.
b. Decrease capacity by 1% for each 2°F decrease in subcooling.
3. Maximum recommended condensing temperature is 140°F.
COOLING PERFORMANCE DATA
OUTDOOR UNIT MODEL NO.
INDOOR COIL MODEL NO.
ID CFM
AIR TEMP.
ENTERING
ID DB (°F)
OUTDOOR UNIT (°F)
ID WB (°F)
55
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (OUTDOOR + INDOOR).
Green shaded cells are ACCA (TVA) conditions.
Blue shaded cells are AHRI conditions.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
76
55 °F
65 °F
P (PSIG)
MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW
107
27.7 1.70 26.3 1.89 24.9 2.09 23.5 2.31 22.0 2.57 20.4 2.88 18.7 3.24 16.8 3.67
118
30.6 1.69 29.0 1.88 27.5 2.08 26.0 2.30 24.4 2.55 22.7 2.85 20.9 3.21 18.9 3.62
130
33.7 1.68 31.9 1.87 30.3 2.07 28.6 2.29 27.0 2.54 25.2 2.84 23.3 3.19 21.2 3.58
142
37.0 1.67 35.1 1.86 33.3 2.06 31.5 2.28 29.7 2.53 27.8 2.82 25.7 3.16 23.6 3.55
156
40.6 1.66 38.5 1.86 36.5 2.06 34.6 2.28 32.6 2.52 30.6 2.81 28.4 3.14 26.1 3.52
TW4B3022S
CF30BXA1
800
80
80
75
57
62
62
T.C.
28.0
30.4
29.8
S.C.
27.7
24.8
21.0
KW
1.61
1.62
1.63
T.C.
27.1
29.1
29.2
S.C.
26.9
24.3
20.8
KW
1.77
1.78
1.78
T.C.
26.3
27.8
28.7
S.C.
26.0
23.8
20.5
KW
1.93
1.94
1.94
T.C.
25.1
26.9
27.3
S.C.
24.8
23.4
19.9
KW
2.16
2.15
2.16
T.C.
23.9
25.9
26.0
S.C.
23.6
23.0
19.2
KW
2.38
2.37
2.38
T.C.
22.4
24.1
24.2
S.C.
22.2
21.9
18.3
KW
2.78
2.77
2.81
T.C.
21.1
22.4
22.4
S.C.
20.9
20.8
17.5
KW
3.16
3.16
3.22
T.C.
19.7
20.6
20.6
S.C.
19.5
19.8
16.6
KW
3.55
3.55
3.63
Outdoor Ambient Temperature
75 °F
85 °F
1000
80
80
80
80
75
67
72
57
62
62
33.2
36.3
29.3
31.8
31.1
20.7
16.6
29.0
27.6
22.9
1.63
1.64
1.69
1.70
1.70
31.9
35.6
28.7
30.5
30.5
20.3
16.2
28.4
27.1
22.8
1.79
1.80
1.85
1.85
1.86
30.6
34.9
28.0
29.1
29.9
19.9
15.9
27.7
26.6
22.8
1.94
1.96
2.00
2.01
2.02
29.6
33.0
26.9
28.1
28.6
19.6
15.5
26.6
26.0
22.1
2.16
2.17
2.23
2.22
2.23
28.6
31.1
25.8
27.1
27.2
19.3
15.0
25.5
25.5
21.4
2.37
2.37
2.45
2.44
2.45
26.6
29.4
24.1
25.4
25.2
18.3
14.3
23.9
24.1
20.5
2.75
2.73
2.82
2.81
2.86
24.7
27.7
22.5
23.8
23.3
17.4
13.7
22.3
22.6
19.6
3.11
3.07
3.18
3.18
3.25
22.8
25.9
21.0
22.2
21.3
16.5
13.0
20.8
21.2
18.7
3.48
3.41
3.54
3.54
3.64
95 °F
105 °F
115 °F
1200
80
80
80
80
75
67
72
57
62
62
34.5
36.6
30.6
33.2
32.5
22.4
17.3
30.3
30.4
24.7
1.71
1.72
1.77
1.77
1.78
33.2
35.9
30.2
31.8
31.8
22.2
17.2
29.9
29.9
24.9
1.86
1.88
1.92
1.93
1.93
31.8
35.3
29.7
30.3
31.1
22.0
17.1
29.4
29.3
25.0
2.02
2.04
2.08
2.08
2.09
30.8
33.7
28.7
29.3
29.8
21.7
16.7
28.4
28.7
24.3
2.23
2.24
2.29
2.30
2.31
29.8
32.0
27.7
28.3
28.4
21.4
16.3
27.4
28.0
23.6
2.44
2.45
2.51
2.51
2.52
27.7
30.1
25.8
26.8
26.3
20.5
15.6
25.6
26.2
22.6
2.81
2.80
2.86
2.86
2.91
25.6
28.3
24.0
25.3
24.2
19.6
15.0
23.8
24.5
21.7
3.16
3.13
3.19
3.19
3.28
23.6
26.4
22.2
23.8
22.1
18.7
14.4
22.0
22.7
20.8
3.52
3.47
3.53
3.53
3.65
Johnson Controls Ducted Systems
125 °F
80
80
67
72
35.9
36.8
24.1
17.9
1.79
1.80
34.5
36.3
24.1
18.1
1.94
1.96
33.0
35.7
24.1
18.3
2.10
2.11
32.0
34.3
23.8
17.9
2.31
2.32
31.0
33.0
23.5
17.5
2.51
2.53
28.7
30.9
22.6
16.9
2.87
2.87
26.5
28.9
21.7
16.3
3.22
3.20
24.4
26.9
20.8
15.7
3.56
3.53