Performance Data - 1.5 Ton - York LX Series Technical Manual

Hide thumbs Also See for LX Series:
Table of Contents

Advertisement

PERFORMANCE DATA - 1.5 TON

CONDENSER-ONLY DATA (OUTDOOR UNIT)
SATURATED SUCTION
@ COMPRESSOR
MODEL
T (°F)
35
40
TW4B1821S
45
50
55
Notes:
1. For Outdoor Unit (Condenser) performance only. Data does not include the effects of air handler power or heat.
2. Performance based on 15°F subcooling and 15°F superheat at the Outdoor Unit base valves.
a. Increase capacity by 1% for each 2°F increase in subcooling.
b. Decrease capacity by 1% for each 2°F decrease in subcooling.
3. Maximum recommended condensing temperature is 140°F.
COOLING PERFORMANCE DATA
OUTDOOR UNIT MODEL NO.
INDOOR COIL MODEL NO.
ID CFM
AIR TEMP.
ENTERING
ID DB (°F)
OUTDOOR UNIT (°F)
ID WB (°F)
55
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (OUTDOOR + INDOOR).
Green shaded cells are ACCA (TVA) conditions.
Blue shaded cells are AHRI conditions.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Johnson Controls Ducted Systems
55 °F
65 °F
P (PSIG)
MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW
107
17.0 0.82 16.2 0.94 15.4 1.06 14.5 1.20 13.6 1.35 12.6 1.53 11.6 1.73 10.6 1.96
118
18.8 0.80 17.9 0.92 17.0 1.05 16.0 1.18 15.0 1.33 14.0 1.51 12.9 1.72 11.8 1.95
130
20.7 0.78 19.7 0.90 18.7 1.03 17.7 1.17 16.6 1.32 15.5 1.49 14.3 1.70 13.1 1.93
142
22.8 0.76 21.7 0.88 20.6 1.01 19.5 1.15 18.3 1.30 17.1 1.48 15.8 1.68 14.5 1.90
156
24.9 0.74 23.8 0.86 22.6 0.99 21.3 1.13 20.1 1.28 18.8 1.46 17.4 1.66 16.0 1.88
TW4B1821S
CF18AXA1
450
80
80
75
57
62
62
T.C.
16.0
18.2
18.3
S.C.
14.6
13.7
11.9
KW
0.97
0.96
0.95
T.C.
15.4
17.5
17.6
S.C.
14.2
13.3
11.5
KW
1.07
1.07
1.06
T.C.
14.8
16.8
16.9
S.C.
13.9
12.8
11.1
KW
1.17
1.17
1.16
T.C.
14.5
16.2
16.3
S.C.
13.7
12.6
10.8
KW
1.30
1.30
1.30
T.C.
14.2
15.6
15.7
S.C.
13.6
12.4
10.6
KW
1.43
1.43
1.43
T.C.
13.4
14.7
14.8
S.C.
12.9
12.0
10.2
KW
1.67
1.66
1.66
T.C.
12.7
13.9
13.9
S.C.
12.3
11.7
9.8
KW
1.90
1.88
1.88
T.C.
11.9
13.1
13.0
S.C.
11.7
11.3
9.4
KW
2.14
2.10
2.10
Outdoor Ambient Temperature
75 °F
85 °F
600
80
80
80
80
75
67
72
57
62
62
20.3
22.0
17.4
19.1
19.3
12.0
9.6
16.5
15.8
13.5
0.94
0.94
1.02
1.01
1.00
19.5
21.3
16.7
18.4
18.5
11.6
9.3
15.9
15.3
13.0
1.05
1.04
1.12
1.11
1.11
18.7
20.6
16.1
17.6
17.7
11.2
9.0
15.4
14.8
12.6
1.15
1.14
1.22
1.22
1.21
18.0
19.8
15.7
16.9
17.0
10.9
8.7
15.1
14.5
12.3
1.29
1.28
1.35
1.35
1.34
17.4
19.0
15.3
16.2
16.4
10.6
8.5
14.8
14.1
12.1
1.43
1.41
1.48
1.48
1.48
16.5
18.1
14.6
15.4
15.4
10.3
8.2
14.1
13.6
11.8
1.64
1.62
1.70
1.70
1.70
15.6
17.2
13.9
14.6
14.5
10.0
7.9
13.4
13.1
11.4
1.85
1.82
1.92
1.91
1.91
14.7
16.3
13.1
13.8
13.6
9.7
7.6
12.8
12.6
11.1
2.05
2.03
2.14
2.12
2.13
5753883-BTG-C-0221
95 °F
105 °F
115 °F
750
80
80
80
80
75
67
72
57
62
62
21.1
22.6
18.7
20.0
20.2
13.4
10.4
18.5
17.9
15.1
1.00
1.00
1.06
1.06
1.05
20.3
22.0
18.1
19.2
19.4
13.1
10.2
17.6
17.3
14.6
1.10
1.09
1.16
1.16
1.16
19.6
21.4
17.5
18.4
18.5
12.8
10.0
16.8
16.7
14.1
1.20
1.19
1.26
1.26
1.26
18.8
20.5
17.0
17.7
17.8
12.4
9.7
16.4
16.3
13.8
1.34
1.33
1.39
1.39
1.39
18.0
19.7
16.5
16.9
17.1
12.0
9.4
15.9
15.8
13.6
1.48
1.46
1.53
1.53
1.53
17.0
18.7
15.7
16.0
16.1
11.7
9.1
15.2
15.2
13.3
1.68
1.67
1.74
1.74
1.74
16.1
17.7
15.0
15.2
15.1
11.4
8.8
14.6
14.6
13.0
1.89
1.87
1.94
1.94
1.94
15.1
16.8
14.3
14.4
14.2
11.2
8.5
13.9
14.0
12.7
2.09
2.07
2.14
2.14
2.15
125 °F
80
80
67
72
21.8
23.3
14.8
11.2
1.05
1.05
21.1
22.7
14.6
11.1
1.15
1.15
20.4
22.2
14.4
11.0
1.25
1.24
19.5
21.3
13.9
10.6
1.39
1.38
18.6
20.3
13.4
10.3
1.52
1.51
17.6
19.3
13.1
10.0
1.73
1.72
16.6
18.3
12.9
9.6
1.93
1.92
15.6
17.3
12.6
9.3
2.13
2.12
65

Advertisement

Table of Contents
loading

Table of Contents