P
H
LUME KIT FOR USE WITH
ORIZONTAL CONCENTRIC FLUE
No
1
CONCENTRIC BEND 90°-PP
2
CONCENTRIC HORIZONTAL PLUME KIT TERMINAL -PP
3
EXTENSION -PP CUTABLE (1000mm)
4
BEND 90°-PP
5
PLUME KIT BIRD GUARD
6
PLUME KIT FLUE EXIT-PP
7
WALL CLAMP
A
INTERNAL DIAMETER
B
EXTERNAL DIAMETER
The plume kit must not be used to correct an illegal terminal location
Item No
LG800012A
BEND 90° Ø80mm PP BLACK EXTERNAL
LG800014A
EXTENSION Ø80mm (1000mm) PP BLACK EXTERNAL
Maximum flue length = Standard flue kit plus 4 additional 1000mm lengths
Maximum number of additional bends allowed = 3
Even if using less than the maximum number of bends, the maximum pipe length may not be exceeded. Even if using less
than the maximum pipe length, the maximum number of bends may not be exceeded.
Description
Additional Flue Ancillary Items all Models
Description
Maximum Flue Lengths
Plume management kit
LG800008A
PLUME MANAGEMENT KIT Ø80/125mm
All models
Ø80/125mm
Ø80/125mm
Ø80mm
Ø80mm
Ø80mm
Ø80mm
Ø80mm
Ø80mm
Ø125mm
Dimensions
N/A
1000mm