COMMON FLUE SYSTEMS

Any installations using flue type C63 must be designed and installed in compliance with any local
Building or planning regulations, but as these systems use a flue system not supplied by Lochinvar,
Lochinvar cannot comment / advise or provide support on the design of this type of flue system. To
design such a flue system, the installer/contractor must consult a specialist flue supplier who will be
responsible for the design and installation of the separate flue system. When designing the type C63
flue system, the instructions in the Installation Manual, provided with the water heater, must be
considered. Lochinvar will provide pressure loss figures for the specific units, but other than that,
Lochinvar cannot provide support on Common Flue requests because flue certification is limited to the
certified categories in the table on page 2. Lochinvar cannot accept any responsibility for Flue system
design.
LGC-...-210
LGC-...-350
LGC-...-420
LGC-...-560
Maximum pressure
Inlet only
Pinlet
Poutlet
[Pa]
[Pa]
-41
0
-74
0
-108
0
-192
0
Outlet only
Pinlet
Poutlet
[Pa]
[Pa]
0
33
0
59
0
108
0
192
Inlet + outlet
Pinlet
Poutlet
[Pa]
[Pa]
-25
23
-44
41
-56
56
-100
100
Page 9 of 11