Indoor Unit Installation
Concrete
Hole in anchor
Hole in plug
Suspension bolt(3/8" or M10)
Ceiling support
12
E-
It is recommended to install the Y-joint before installing the indoor unit.
1
Place the pattern sheet on the ceiling at the spot where you want to
install the indoor unit.
Note
Since the diagram is made of paper, it may shrink or stretch
slightly due to temperature or humidity. For this reason,
before drilling the holes maintain the correct dimensions
between the markings.
2
Insert bolt anchors, use existing ceiling supports or construct a suitable
support as shown in figure.
Insert
3
Install the suspension bolts depending on the ceiling type.
CAUTION
Ensure that the ceiling is strong enough to support
the weight of the indoor unit. Before hanging the unit,
test the strength of each attached suspension bolt.
If the length of suspension bolt is more than 1.5m,
it is required to prevent vibration.