Terminal number
M3 screw (Transmission /X1, X2)
(Remote controller /Y1, Y2)
To peel the film from the lead cable, use a dedicated tool that will not damage the
conductor cable.
When installing a screw on the terminal block, do not cut the cable by overtightening the
screw. On the other hand, an undertightened screw can cause faulty contact, which will
lead to a communication failure.

6.4. Connection of wiring

(1) Remove the control box cover and install each connection cable.
Attach the conduit connector on
the wiring connecting port.
(The grommet edging and the
connection cable clamp are not
used.)
Wiring
connect-
ing port (for
transmission cable
and remote controller
cable)
Lock nut
Tightening torque
4.4 to 5.3 Ibf·in (0.5 to 0.6 N·m)
CAUTION
Conduit connector
Lock nut
Wiring connecting port
(for power supply cable)
Wiring cover
Control box cover
L2
L1
(N)
Earth
(ground)
Conduit connector
(L1, L2 (N): Power supply cable)
(2) Please firmly tighten Connection cable and Remote controller cable with the attached
cable tie.
Push mount cable tie (accessories)
(3) Replace the Control box
cover and Wiring cover.
Securely tighten the
screws.
Cure the wiring connecting
port and remote controller
connecting port with putty or
heat insulation so that insects
or dust will not enter the unit.
Do not bundle the remote controller cable, or wire the remote controller cable in parallel,
with the indoor unit connection wire (to the outdoor unit) and the power supply cable. It
may cause erroneous operation.
(4) Fix the conduit with the supporters as shown below.
Conduit (Power supply cable)
Indoor unit
30 in
54 in
(756 mm)
(1,361 mm)
or less
or less
X1, X2: Transmission cable
Cut
Y1, Y2: Remote controller cable
(do not use Y3.)
CAUTION
Supporter
54 in
54 in
(1,361 mm)
(1,361 mm)
or less
or less
En-8