A. For solid core wiring
(1) To connect the electrical terminal, follow the below diagram and connect after looping
it around the end of the cable.
(2) Use the specifi ed cables, connect them securely, and fasten them so that there is no
stress placed on the terminals.
(3) Use an appropriate screwdriver to tighten the terminal screws. Do not use a
screwdriver that is too small, otherwise, the screw heads may be damaged and
prevent the screws from being properly tightened.
(4) Do not tighten the terminal screws too much, otherwise, the screws may break.
(5) See the table for the terminal screw tightening torques.
(6) Please do not fi x 2 power supply cables with 1 screw.
Strip 1 in
(25 mm)
Screw with
special washer
Cable
Cable end (Loop)
Terminal block
When using solid core cables, do not use the ring terminal. If you use the solid core
cables with the ring terminal, the ring terminal's pressure bonding may malfunction
and cause the cables to abnormally heat up.
B. For strand wiring
(1) Use ring terminals with insulating sleeves as shown in the fi gure below to connect to
the terminal block.
(2) Securely clamp the ring terminals to the cables using an appropriate tool so that the
cables do not come loose.
(3) Use the specifi ed cables, connect them securely, and fasten them so that there is no
stress placed on the terminals.
(4) Use an appropriate screwdriver to tighten the terminal screws. Do not use a
screwdriver that is too small, otherwise, the screw heads may be damaged and
prevent the screws from being properly tightened.
(5) Do not tighten the terminal screws too much, otherwise, the screws may break.
(6) See the table for the terminal screw tightening torques.
(7) Please do not fi x 2 power supply cables with 1 screw.
Strip 3/8 in
(10 mm)
Screw with
special washer
Cable
Ring terminal
Terminal block
Use ring terminals and tighten the terminal screws to the specifi ed torques, otherwise,
abnormal overheating may be occurred and possibly cause serious damage inside the
unit.
Tightening torque
M4 screw
(Power supply/L1, L2 (N), GND)
6.3.2. Transmission and Remote controller cable
Transmission cable
Shielded cable (no fi lm)
Remote controller cable
For 3-wire type
1 in (25 mm)
Loop
Screw with
special washer
Cable end (Loop)
Cable
WARNING
Ring terminal
Sleeve
Screw with
special washer
Ring terminal
Cable
WARNING
11 to 16 lbf·in
(1.2 to 1.8 N·m)
1 in (25 mm)
1-3/8 in (35 mm)
For 2-wire type
1 in (25 mm)
• When the 2 cables are attached.
GOOD
Different diameter
Tighten the terminal screws to the specifi ed torques, otherwise, abnormal overheating
may be occurred and possibly cause serious damage inside the unit.
Tightening torque
M3 screw
(Transmission/X1, X2)
(Remote controller/Y1, Y2, Y3)
To peel the fi lm from the lead cable, use a dedicated tool that will not damage the
conductor cable.
When installing a screw on the terminal block, do not cut the cable by overtightening
the screw. On the other hand, an undertightened screw can cause faulty contact, which
will lead to a communication failure.

6.4. Connection of wiring

(1) Remove the control box cover and install each connection cable.
Control box cover
Loosen the screws.
(4 screws)
(2) After wiring is complete, clamp the remote controller cable, transmission cable and
power supply cable with cable tie.
When switching the DIP switch (SW1), be sure to turn off the power supply to the
indoor unit. Otherwise, the PC board of the indoor unit may be damaged.
PROHIBITED
Connect to 1 side
WARNING
4.4 to 5.3 lbf·in
(0.5 to 0.6 N·m)
CAUTION
CAUTION
En-8