GENERAL DESCRIPTION

control unit is a fire detection control unit manufactured in conformity with theEN 54-2 and
MA-2000
EN 54-4 rules.
Technical features:
Multi-microprocessor system with 7" / 17,78 cm TFT display (800 x 480 with backlit), 256 colors touchscreen with
keyboard simulation to program and configure the system and the following specific functions:
End Delay, Silence Buzzer, Silence/Resound, Reset, Evacuation.
Detection LINES:
2 analogue loops programmable to closed or open loop for the connection of the field elements.
Each loop can drive 99 detectors + 99 input and output modules with Morley / System sensor protocol.
POWER SUPPLY:
Input: 100 ... 120 V AC, 50 / 60 Hz, max. 3,0 A
200 ... 240 V AC, 50 / 60 Hz, max. 1,7A
Voltage: 24 V DC / max. 6,25 A
User output: 28 V DC (+ 3 % +/- 18 %) 1 A, on board to power external loads such as sirens, bells, etc.
Primary Power Section:
- I max. A 1,91 A
- I max. B 2,7 A
- I min. 341 mA (with typical loop load connected)
Fuse: 230 V AC / 3,15 A
OUTPUTS:
1 Supervised Sounder Output (EOL 4
1 General Alarm Output with contacts free from voltage / supervised Output (EOL 4
1 General Fault Output with contacts free from voltage
2 Optional outputs with contacts free from voltage / supervised Output (EOL 4
Mechanics
The control unit mechanics is suitable for wall installations.
For cabinet sizes refer to the below drawing "MA-2000 dimensions"
Protection grade: IP 30
Operation temperature: -5 °C ... +40 °C
Storage temperature
Weight: 7 Kg
Main Functions
3 password levels (Operator - Maintenance – Configuration)
4 total access levels in conformity with the EN 54 rules
40 zonal indicators on screen display
Programmable text: point description through 32 characters; zone description through 32 characters
2000 physical zones, 800 logical equation, 400 logical groups (stand-alone), 1600 logical groups (network)
CBE Control Equations (Control-by event) for activation with logical operators (and, or etc.)
History Event file with the last 10.000 events in non-volatile memory
Real time clock
Line self-programming with automatic recognition of the type of the connected devices
Automatic recognition of points having the same address
Decision algorithms for the alarm and fault criteria
Automatic sensitivity changes Daytime /Night
Signalling of need for sensor cleaning
Signalling of poor sensor sensitivity
Programmable alarm threshold for sensors
Pre-defined software function programming for the various devices used
Walk-Test function for zones
M-167.1-MA2000-EN / 06.2022
7KΩ or Diode)
: -10 °C ... +50 °C
MA-2000
7 KΩ or Diode)
7 KΩ or Diode)
9