Honeywell VISTA-50P Installation And Setup Manual

Honeywell VISTA-50P Installation And Setup Manual

Ademco vista series
Hide thumbs Also See for VISTA-50P:
Table of Contents

Advertisement

$
'
(
0
&
2
9
,
6
7
$
6
(
5
,
(
6
$
'
(
0
&
2
9
,
6
7
$
6
(
5
,
(
6
9
,
6
7
$



3

9
,
6
7
$



3
8
/
9
,
6
7
$



3

9
,
6
7
$



3
8
/
&RPPHUFLDO %XUJODU\
3DUWLWLRQHG 6HFXULW\ 6\VWHP
:LWK 6FKHGXOLQJ
,QVWDOODWLRQ DQG 6HWXS *XLGH
WWW.DIYALARMFORUM.COM
N5944-6V2 5/04 Rev A

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell VISTA-50P

  • Page 1 & & &RPPHUFLDO %XUJODU\ 3DUWLWLRQHG 6HFXULW\ 6\VWHP :LWK 6FKHGXOLQJ ,QVWDOODWLRQ DQG 6HWXS *XLGH WWW.DIYALARMFORUM.COM N5944-6V2 5/04 Rev A...
  • Page 2 WWW.DIYALARMFORUM.COM...
  • Page 3: Table Of Contents

    • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • List of Figures ............................v Conventions Used in This Manual..................... vi SECTION 1: General Description ..................... 1-1 About the VISTA-50P/VISTA-50PUL ..........................1-1 Features .....................................1-1 SECTION 2: Partitioning ........................2-1 Theory of Partitioning .................................2-1 Setting-Up a Partitioned System ............................2-1...
  • Page 4 Table of Contents Daily Open/Close Schedules..............................6-6 Holiday Schedules................................6-6 Time-Driven Events................................6-7 Limitation of Access Schedules............................6-10 Temporary Schedules ..............................6-11 User Scheduling Menu Mode ............................6-12 SECTION 7: Downloading Primer ....................7-1 General Information ................................7-1 Getting On-Line with a Control Panel..........................7-2 Direct-Wire Downloading..............................7-3 Telco Handoff..................................7-3 SECTION 8: Setting the Real-Time Clock..................
  • Page 5: List Of Figures

    Figure 3-14: Wiring a 333PRM using a 4204 and a Power Supply ..................3-10 Figure 3-15: Wiring Latching Glassbreaks to Zone 8 ......................3-10 Figure 3-16: Polling Loop Connections to the VISTA-50P/VISTA-50PUL................3-12 Figure 3-17: Polling Loop Connections Using One 4297 Extender Module ................3-12 Figure 3-18: Polling Loop Connections Using Multiple Extender Modules................3-13...
  • Page 6: Conventions Used In This Manual

    Conventions Used in This Manual • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Before you begin using this manual, it is important that you understand the meaning of the following symbols (icons).
  • Page 7: Section 1: General Description

    Supports the 4285/4286 VIP Module, which allows access to the system from either a remote location or on the premises The VIP Module is not Listed for use with the VISTA-50P/VISTA-50PUL Control Panel in a UL installation. • Supports the 4146 Keyswitch on any one of the system’s 8 partitions.
  • Page 8 86 zones, as well as openings and closings for all 75 users. This requires central stations to be equipped with the 685 receiver using software level 4.10 or higher to fully support all new VISTA-50P/VISTA-50PUL report codes. If you need to update your 685 receiver, contact your distributor.
  • Page 9: Section 2: Partitioning

    S E C T I O N Partitioning • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Theory of Partitioning This system provides the ability to arm and disarm up Users...
  • Page 10 VISTA-50P/VISTA-50PUL Installation and Setup Guide 1*18 Affects Lobby (must be programmed by User #1 has access to Office #1 and the Common Lobby. partition) User #2 has access to Office #2 and the Common Lobby. Setting this field to 1 for a specific partition causes that...
  • Page 11: Master Keypad Setup And Operation

    Section 3 - Installing the Control Other Methods of Arming/Disarming Auto-Arming/Disarming Common Lobby logic remains active when arming or If scheduling is used to automatically arm and/or disarming a partition that affects and/or arms the disarm partitions, the common lobby partition does not common lobby in one of the following manners: automatically follow another partition that is programmed to arm or disarm the lobby.
  • Page 12 VISTA-50P/VISTA-50PUL Installation and Setup Guide WWW.DIYALARMFORUM.COM...
  • Page 13: Section 3: Installing The Control

    S E C T I O N Installing the Control • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • This section describes the procedures for mounting and wiring the control panel and all the peripheral devices.
  • Page 14: Grade A Mercantile Safe And Vault Listing Guidelines

    VISTA-50P/VISTA-50PUL Installation and Setup Guide (Shows typical local Grade A listing installation) RUN BELL WIRES IN CONDUIT PLUG THIS KNOCKOUT TO PLUG AN UNUSED KNOCKOUT OPENING, REMOVE KNOCKOUT AND INSTALL A PAIR OF CLIP-ON DOOR DISC PLUGS AND A CARRIAGE BOLT AS SHOWN.
  • Page 15: Installing The Keypads

    Section 3 - Installing the Control Installing the Keypads • Up to 16 addressable keypads (addresses 00-30) Addressing the Keypads may be used (you may need to use an auxiliary power supply if the 750mA aux. output is The keypads will not operate until they are exceeded).
  • Page 16: Installing External Sounders

    VISTA-50P/VISTA-50PUL Installation and Setup Guide Installing External Sounders The VISTA-50P/VISTA-50PUL provides a bell circuit Non-UL Installations output for operating fire and burglary alarm For non-UL installations, the total current drawn from notification appliances. The alarm output is rated as this output can be up to 1.7 amps. A battery must be follows: 10VDC –...
  • Page 17: Figure 3-6: Wiring Polarized Fire Devices

    Section 3 - Installing the Control ALARM SOUNDER OUTPUT: 1-VDC - 13.8VDC 1.7A MAXIMUM BELL HORN Figure 3-6: Wiring Polarized Fire Devices POLARIZING DIODES (MUST MOUNT AT INDICATING DEVICE) PANEL BELL HORN OTHER BELL BELL DEVICES PANEL BELL NONPOLARIZED BURGLARY POLARIZED FIRE INDICATING DEVICES INDICATING DEVICE...
  • Page 18: Telephone Line Connections

    VISTA-50P/VISTA-50PUL Installation and Setup Guide Telephone Line Connections To prevent the risk of shock, disconnect Connect the main dialer output to telephone company phone lines at the telco jack before servicing. lines using the RJ31X cables supplied. If the communicator is connected to a PABX,...
  • Page 19: Figure 3-9: Wiring Connections For Zones 1-9

    VISTA-50P/VISTA-50PUL Installation and Setup Guide Red Jumper ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 ZONE 7 ZONE 8 ZONE 9 ZONE 1 N.C. N.C. N.C. N.C. N.O. N.O. N.O. N.O. 2k EOLR 2k EOLR 2k EOLR 2k EOLR...
  • Page 20: Figure 3-11: 4-Wire Smoke Detectors

    VISTA-50P/VISTA-50PUL Installation and Setup Guide Using 4-Wire Smoke Detectors on Zones 1-8 Power to 4-wire smoke detectors must be supervised with an EOL device (use a System You may use as many 4-wire smoke detectors as can be Sensor A77-716B EOL relay module powered from the panel’s Auxiliary Power output...
  • Page 21: Figure 3-12: Wiring A 333Prm To The Control

    VISTA-50P/VISTA-50PUL Installation and Setup Guide CONTROL PANEL MOMENTARY RESET SWITCH – 4-WIRE SMOKE EOL POWER DETECTORS SUPERVISION RELAY MODULE A77-761B SHOWN POWERED. RELAY OPENS WHEN POWER IS LOST 2000 JUMPER EOLR HEAT DETECTOR JUMPER P1 ON 333 MODULE MUST BE IN "B"...
  • Page 22: Figure 3-14: Wiring A 333Prm Using A 4204 And A Power Supply

    VISTA-50P/VISTA-50PUL Installation and Setup Guide CONTROL PANEL – 4-WIRE SMOKE EOL POWER DETECTORS SUPERVISION RELAY MODULE A77-761B SHOWN POWERED. RELAY OPENS WHEN POWER IS LOST JUMPER P1 ON 333 MODULE MUST BE IN 2000 JUMPER "B" POSITION EOLR HEAT DETECTOR...
  • Page 23: Installing Rpm Devices

    4192CP Ionization Smoke Detector 1. Go to the honeywell.com/security website 4101SN Serial Number Single-Output Relay Module 2. Click the Honeywell Security & Custom Electronics link. 4208U Universal 8-Zone Expander 4939SN-BR Serial Number Surface-Mount Reed 3. Click the Commercial link.
  • Page 24: Figure 3-16: Polling Loop Connections To The Vista-50P/Vista-50Pul

    VISTA-50P/VISTA-50PUL Installation and Setup Guide Step Action Polling Loop Supervision Wire each device to the polling loop, making A short on the polling loop is indicated by a trouble on sure of the correct polarity (refer to the zone 97 and reports as a trouble condition only. If device’s instructions).
  • Page 25: Wireless Zone Expansion

    Section 3 - Installing the Control EXTENSION POLLING LOOP #1 • DO NOT CONNECT 4297 MODULES IN SERIES (i.e., DO NOT CONNECT ONE 4297 MODULE'S EXTENSION LOOP TO ANOTHER MODULE'S INPUT LOOP.) CONTROL PANEL INPUT POLLING LOOP EXTENSION POLLING LOOP #2 4297 COMBINED INPUT AND EXTENSION LOOP LIMITS: •...
  • Page 26: Figure 3-19: Installing The 5881Enhc With Tamper Protection

    VISTA-50P/VISTA-50PUL Installation and Setup Guide RF System Installation Advisories To install the 5881 RF receiver, perform the following • steps: Place the receiver in a high, centrally located area. Do not place it on or near metal objects. This will...
  • Page 27: Figure 3-20: 5881 Rf Receiver (Cover Removed)

    Section 3 - Installing the Control ANTENNAS TO CONTROL'S REMOTE KEYPAD CONNECTION POINTS. USE MAX. of 220 ft. [67m of #22 (0.64mm) WIRE or 550 ft. (168m) of #18 (1mm) WIRE INSERT IN CIRCUIT FOR EACH RUN. OBSERVE 20 ft. MAX. RIGHT-HAND BOARD FOR COMMERCIAL FIRE INSTALLATIONS.
  • Page 28 VISTA-50P/VISTA-50PUL Installation and Setup Guide 5800 Series Transmitter Setup Transmitter Supervision 5800 Series transmitters have the following Supervised RF transmitters send a check-in signal to characteristics: the receiver at 70–90 minute intervals. If at least one • check-in is not received from each supervised Transmitters have built-in serial numbers that transmitter within a programmed period (field 1∗31),...
  • Page 29: Installing Output Devices

    Section 3 - Installing the Control Installing Output Devices The VISTA-50P/VISTA-50PUL support up to 16 To install the relay modules, see Figure 3-21 and outputs. Each device must be programmed as to how to perform the following steps: act (ACTION), when to activate (START), and when to...
  • Page 30: Installing The Ground Start Module

    VISTA-50P/VISTA-50PUL Installation and Setup Guide Installing the Ground Start Module To install the 675 Ground Start Module, perform the following steps: The Ground Start Module is not intended for use in UL Listed applications. Step Action Determine which side of the telephone line...
  • Page 31: Remote Keypad Sounder

    Section 3 - Installing the Control Wiring for the Remote Keyswitch Keyswitch Tamper Operation To install the 4146 keyswitch, perform the following The tamper switch need not be used for fire or UL steps: Household Burglary installations. For UL Commercial Step Action Burglary installations, the tamper switch must be...
  • Page 32: Long Range Radio Connected To The J7 Triggers

    VISTA-50P/VISTA-50PUL Installation and Setup Guide Long Range Radio Connected to the J7 Triggers These triggers may be used to trip auxiliary alarm The fire and burglary/audible panic alarm triggers are signaling equipment such as the 7720, 7720ULF, and normally LOW and go HIGH until a User Code + OFF 7920SE Long Range Radios.
  • Page 33 Section 3 - Installing the Control The 4285/4286 VIP Module features: Step Action • Allows the user to receive synthesized voice Make 12V (+) and (–) and data-in and data- messages over the phone regarding the status of out connections from the VIP Module to the the security system.
  • Page 34: Installing The Audio Alarm Verification Module

    VISTA-50P/VISTA-50PUL Installation and Setup Guide SPEAKER NOTE: IF CONNECTING SINGLE SPEAKER, USE 8-ohm SPEAKER ONLY. IF CONNECTING 2 SPEAKERS, USE 4-ohm or 8-ohm SPEAKERS AND CONNECT IN SERIES. INCOMING TELCO LINE SEE SPEAKER NOTE 4286 VIP MODULE NOTE: GREY RJ31X...
  • Page 35: Figure 3-27: Uvs Connections To The Control Panel

    Section 3 - Installing the Control UVCM AND UVST SUMMARY OF CONNECTIONS Refer to UVS Installation and Setup Guide K4214 for complete information NOTE 1: CONNECT TO PROPER EARTH GROUND. SWITCH BANK 2 SWITCH BANK 1 NOTE 2: POWER MAY ALSO BE SUPPLIED BY A LISTED CLASS 2 FUTURE USE, SET TO ON UVST 1 AUX AUDIO, ON = ENABLED POWER SUPPLY RATED 12VDC, MIN 600mA CONNECTED TO THE...
  • Page 36: Connecting The Transformer

    VISTA-50P/VISTA-50PUL Installation and Setup Guide Connecting the Transformer For Household Burglary-Only Installations: The This product uses the 1361 transformer (1361CN in total current drawn from the alarm output may be up to Canada). If you are using X-10 devices, the 1361X10 1.7A.
  • Page 37: Panel Earth Ground Connections

    Section 3 - Installing the Control Panel Earth Ground Connections • In order for the lightning transient protective devices in AC Power Outlet Ground: Available from 3- this product to be effective, the designated earth ground prong, 120VAC, power outlets only. To test the terminal (terminal 30) must be terminated in a good integrity of the ground terminal, use a three-wire earth ground.
  • Page 38: Determining The Size Of The Standby Battery

    Tables 1 through 3, then add the Alarm Output current subtotal. to get the combined current. Table 3: Alarm Output Current Load Table 4: Total VISTA-50P/VISTA-50PUL Current Load Total Current Total Current Device Device Current X...
  • Page 39 Section 3 - Installing the Control Use the Battery Selection Table to select the Connect the battery, referring to Figure 3-28. appropriate battery for the installation. Table 6: Battery Selection Table The standby battery is automatically tested for Capacity Recommended Battery Comment 10 minutes every 4 hours, beginning 4 hours after exiting Programming mode.
  • Page 40 VISTA-50P/VISTA-50PUL Installation and Setup Guide 3-28 WWW.DIYALARMFORUM.COM...
  • Page 41: Section 4: Programming

    S E C T I O N Programming • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Program Modes The factory-loaded defaults (✳97) enable There are two programming modes for the VISTA-...
  • Page 42: #93 Menu Mode Programming

    VISTA-50P/VISTA-50PUL Installation and Setup Guide Programming System-Wide Data Fields Programming Partition-Specific Data Fields Values for some programming fields are system-wide To program partition-specific data fields once in (global), and some can be different for each partition Program Mode, do the following: (partition-specific).
  • Page 43: Index

    Section 4 – Programming Below is a list of the main menus. For details refer to the VISTA-50P/VISTA-50PUL Programming Guide. MAIN MENU OPTIONS For programming the following: ZONE PROG? • Zone Number 1 = YES 0 = NO • Zone Response Type •...
  • Page 44: Zone Number Designations

    VISTA-50P/VISTA-50PUL Installation and Setup Guide Zone Number Designations The VISTA-50P/VISTA-50PUL supports up to 86 zones Zone Index of hardwire, polling loop and/or wireless protection, The zones are designated as follows: distributed among up to 8 partitions. The following ZONE #...
  • Page 45: Zone Response Type Definitions

    Section 4 – Programming Communication Defaults for Zones ZONE # ZONE # ZONE # ZONE # 92 (DURESS) ALARM RST. TROUBLE TRBLE. RST BYPASS BYP. RST. Zone Response Type Definitions Each zone must be assigned a zone type, which defines Type 02: Entry/Exit #2 Burglary the way in which the system responds to faults in that Provides a secondary entry delay, if the system is...
  • Page 46: Zone Input Type Definitions

    VISTA-50P/VISTA-50PUL Installation and Setup Guide Type 04: Interior Follower Type 09: Supervised Fire (Without Verification) Provides a delayed alarm (using the programmed entry Provides a fire alarm on a short circuit and a trouble delay time) if an entry/exit zone is faulted first.
  • Page 47: Programming For 4100Sm

    1✳71 12/24-Hour Time Stamp (0=12 hr; 1=24 hr) 1✳73 Printer Baud Rate (0=1200; 1=300) Programming for Access Control The VISTA-50P/VISTA-50PUL can be used to trigger an access point (i.e., door strike) for 2 seconds by entering User Code + [0].
  • Page 48 VISTA-50P/VISTA-50PUL Installation and Setup Guide WWW.DIYALARMFORUM.COM...
  • Page 49: Section 5: Data Field Descriptions

    S E C T I O N Data Field Descriptions • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Data Field Programming The following pages list this control’s data fields in numerical order.
  • Page 50 VISTA-50P/VISTA-50PUL Installation and Setup Guide FIELD TITLE and DATA ENTRIES EXPLANATION Exit Delay #2 (partition-specific) Exit Delay #2 is used for a secondary door requiring a longer delay than those assigned to Exit Delay #1. Enter 03-15 multiplied by 15 seconds.
  • Page 51: Ignore Expansion Zone Tamper

    Section 5 – Data Field Descriptions FIELD TITLE and DATA ENTRIES EXPLANATION Ignore Expansion Zone Tamper If disabled, the system monitors the tampers on expansion zones. 0 = disable (tamper detection) NOTE: Only applicable to certain polling loop sensors with tamper 1 = enable (no tamper detection) switches or 5800 Series transmitters.
  • Page 52: Primary Phone Number

    VISTA-50P/VISTA-50PUL Installation and Setup Guide FIELD TITLE and DATA ENTRIES EXPLANATION Primary Phone Number Enter the primary central station phone number, up to 17 digits. This is the phone number the control will use to transmit Alarm and status Enter 0-9; #11 for *, #12 for #, #13 for a 2- messages to the central station.
  • Page 53: Dial Tone Detection

    Section 5 – Data Field Descriptions FIELD TITLE and DATA ENTRIES EXPLANATION Dial Tone Detection If enabled, the system waits for true dial tone. If no dial tone is detected, control dials at end of pause programmed in field *42. 0 = disable 1 = enable If disabled, the system pauses for seconds entered in field *42, then dials.
  • Page 54 VISTA-50P/VISTA-50PUL Installation and Setup Guide FIELD TITLE and DATA ENTRIES EXPLANATION Standard/Expanded Reporting This field has six entries as follows: Alarm, Restore, Bypass, Trouble, Open/Close, Low Battery. If enabled, expanded reports are sent to the Secondary secondary phone number if low speed format is selected in field *47.
  • Page 55 Section 5 – Data Field Descriptions FIELD TITLE and DATA ENTRIES EXPLANATION Alarm Code for Zones 49–56 Skip this field. Use #93 Menu Mode, Zone Programming to program the response types. Refer to the Programming Guide for details. ID Digit for Zones 49–56 Skip this field.
  • Page 56: First Test Report Time

    VISTA-50P/VISTA-50PUL Installation and Setup Guide FIELD TITLE and DATA ENTRIES EXPLANATION First Test Report Time Enter the day and time that the first Test report shall be transmitted. Enter 00 in all locations if the Test report is to be sent immediately upon Enter 00-07the for day (01 = Monday) exiting.
  • Page 57: Lobby Partition

    Section 5 – Data Field Descriptions FIELD TITLE and DATA ENTRIES EXPLANATION Response Types for Zones 81–87 Skip this field. Use #93 Menu Mode, Zone Programming to program the 1*08 response types. Refer to the Programming Guide for details. Response Types for Zones 88–91 Skip this field.
  • Page 58 VISTA-50P/VISTA-50PUL Installation and Setup Guide Cross-Zoning Cross Zoning is designed so that a combination of two zones must be faulted within a 5-minute period of each other (whereas the first zone remains faulted, when the second zone trips) to cause an alarm on either zone. This prevents momentary faults from one of the zones from causing an alarm condition.
  • Page 59: Rf Transmitter Check-In Interval

    Section 5 – Data Field Descriptions FIELD TITLE and DATA ENTRIES EXPLANATION Select when the RF transmitter low-battery condition should display and RF Transmitter Low Battery 1*28 audible beep annunciate on the keypad. Sound Must be 1 for UL installations. 0 = disarmed state only 1 = both armed and disarmed states If enabled, the system sends a Trouble message for RF transmitter low-...
  • Page 60: Call Waiting Defeat

    VISTA-50P/VISTA-50PUL Installation and Setup Guide FIELD TITLE and DATA ENTRIES EXPLANATION This field has seven two-digit entries as follows: Arm STAY, Time/Date Non-Alarm Report Codes Report 1*41 set or Event Log Reset, Event Log 50% or 90% Full, Event Log Overflow, Codes (Second Digit) Exit Error (Zone), Exit Error (User) and Recent Close.
  • Page 61: Zone 5 Audio Alarm Verification

    Section 5 – Data Field Descriptions FIELD TITLE and DATA ENTRIES EXPLANATION If enabled, the system arms/disarms in accordance with the button’s Enable 5800 RF Button Global 1*57 user’s global arming settings. 0 = disable 1 = enable If enabled, allows the RF button user to force a bypass of all faulted zones Enable 5800 RF Button Force 1*58 when arming the system.
  • Page 62 VISTA-50P/VISTA-50PUL Installation and Setup Guide FIELD TITLE and DATA ENTRIES EXPLANATION Daylight Saving Time Start/End Enter the start and end weekends for daylight saving time as follows: 2*02 1=first; 2=second; 3=third; 4=fourth; 5=last; 6=next to last; 7=third from Weekend last. Standard setting for U.S. is 1,5.
  • Page 63: Enable Goto For This Partition

    Section 5 – Data Field Descriptions FIELD TITLE and DATA ENTRIES EXPLANATION This field has eight two-digit entries as follows: Early Opening, Early Scheduling Report Codes Report 2*14 Closing, Late Opening, Late Closing, No Opening (late to open), No Codes (Second Digit) Closing (late to close), Auto-Arm Failure, and Access Schedule Changed.
  • Page 64 VISTA-50P/VISTA-50PUL Installation and Setup Guide 5-16 WWW.DIYALARMFORUM.COM...
  • Page 65: Section 6: Scheduling Options

    S E C T I O N Scheduling Options • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •...
  • Page 66: Time Window Definitions

    VISTA-50P/VISTA-50PUL Installation and Setup Guide Exception Reports Time-Driven Events This option allows the reporting of openings and The system can automatically activate and de-activate closings to the central station only if the arming and relays at predetermined times to turn lights or other disarming occurs outside of the predetermined opening devices on and off.
  • Page 67: Open/Close Schedules Definitions

    Section 6 – Scheduling Options Open/Close Schedules Definitions General Additional Schedules The open/close scheduling is controlled by one of three Additional opening and closing schedules can be schedules. Each schedule consists of one time window programmed using the Time-Driven Event for openings and one time window for closings.
  • Page 68: Scheduling Menu Mode

    VISTA-50P/VISTA-50PUL Installation and Setup Guide Scheduling Menu Mode The #80 Scheduling Menu Mode is used to program Steps to Program Scheduling Options most of the scheduling and timed-event options. Enter Installer Code + [#] + [8] + [0] from the normal This section contains examples of the operating mode.
  • Page 69: Time Windows

    Section 6 – Scheduling Options PROMPT EXPLANATION Enter 1 to program timed events for relay outputs, additional schedules, and other system functions. Refer Timed Events ? to Time-Driven Event Programming later in this section for detailed procedures. 1 = YES 0 = NO Enter 0 to move to the “Access Sched?”...
  • Page 70: Daily Open/Close Schedules

    VISTA-50P/VISTA-50PUL Installation and Setup Guide Daily Open/Close Schedules Each partition can be assigned one daily open/close Open/Close Schedule Worksheet schedule, plus a holiday schedule. Temporary schedules are programmed separately, using the #81 The following worksheet is an example of the worksheet found in the Programming Guide.
  • Page 71: Time-Driven Events

    Section 6 – Scheduling Options Holiday Schedule Worksheet The following worksheet is an example of the worksheet found in the Programming Guide. Partition Month/Day 3…16 Holiday Schedule Programming After entering Scheduling Menu Mode, press [0] until the “Holidays ?” prompt appears. PROMPT EXPLANATION Enter 1 to program holiday schedules.
  • Page 72 VISTA-50P/VISTA-50PUL Installation and Setup Guide Enter the schedule number (01-20) and time Bypass Commands window number (01-20), and note the day of the Action Code Action Action Specifier week the action is desired. Auto bypass – Zone list Zone list # Enter the code for the desired action and Auto unbypass –...
  • Page 73 Section 6 – Scheduling Options After entering Scheduling Menu Mode, press [0] until the “Timed Events ?” prompt appears. PROMPT EXPLANATION Enter 1 to program timed events. Timed Events ? 1 = YES 0 = NO Enter the timed event number to be programmed (01-20). TIMED EVENT # ? Press [✳].
  • Page 74: Limitation Of Access Schedules

    VISTA-50P/VISTA-50PUL Installation and Setup Guide PROMPT EXPLANATION Enter the time window number (01-20) for which this timed event is to occur. As the number is keyed in, the 01 Time Window ? actual time that has been stored for the time window number is displayed.
  • Page 75: Temporary Schedules

    Section 6 – Scheduling Options PROMPT EXPLANATION Enter the access control schedule number between 01 and 08. ACCESS SCHED # ? Press [✳] to accept entry. 01-08, 00 = Quit 01 Enter 00 at the “Access Sched #?” prompt to quit the access control menus and display the Quit ? prompt. Enter the first time-window number (01-20) for this access schedule for the displayed day.
  • Page 76: User Scheduling Menu Mode

    VISTA-50P/VISTA-50PUL Installation and Setup Guide Temporary Schedules Programming Enter User Code + [#] + 81 to enter this mode. PROMPT EXPLANATION This prompt is for entering the start and end times of the disarm (opening) window for Monday. Mon DISARM WIND.
  • Page 77 Section 6 – Scheduling Options PROMPT EXPLANATION If that timer number has already been programmed, a summary screen appears. In this example: 06 07:00P 11:45P 06 = Timer # PORCH LITE 07:00PM = Start Time 11:45PM = Stop Time PORCH LITE = Descriptor for Output Device # 4 04 = Output Device # affected by this timer Press [✳] to continue.
  • Page 78 VISTA-50P/VISTA-50PUL Installation and Setup Guide 6-14 WWW.DIYALARMFORUM.COM...
  • Page 79: Section 7: Downloading Primer

    COMPASS DOWNLOADING software available on downloading software User Manual. CD ROM with a complete User’s Manual. It may NOTES: also be downloaded from the Honeywell web page. • Each time the control panel is accessed The web address is www.honeywell.com/security.
  • Page 80: Getting On-Line With A Control Panel

    VISTA-50P/VISTA-50PUL Installation and Setup Guide Getting On-Line with a Control Panel At the protected premises, the control panel must be To download a control without programming any connected to the existing telephone line (refer to information, perform the following steps: SECTION 3: Installing the Control).
  • Page 81: Direct-Wire Downloading

    Section 24 - Downloading Primer Direct-Wire Downloading The VISTA-50P/VISTA-50PUL can be downloaded Connector J8 on the main PC board (see the Summary without using a modem or telephone line by using a of Connections diagram on the inside back cover of this...
  • Page 82 VISTA-50P/VISTA-50PUL Installation and Setup Guide WWW.DIYALARMFORUM.COM...
  • Page 83: Section 8: Setting The Real-Time Clock

    S E C T I O N Setting the Real-Time Clock • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • General Information Use a 6139/6160 alpha keypad to set the real- This system provides a real-time clock, which must be...
  • Page 84 VISTA-50P/VISTA-50PUL Installation and Setup Guide WWW.DIYALARMFORUM.COM...
  • Page 85: Section 9: User Access Codes

    • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • General Information The VISTA-50P/VISTA-50PUL allows a total of 75 The Quick Arm feature can also be programmed security access codes to be allocated.
  • Page 86: Multiple Partition Access

    VISTA-50P/VISTA-50PUL Installation and Setup Guide Level 6: Duress Codes Duress Reporting NOTE: A non-zero report • Sends a silent alarm to a central monitoring station code for zone 92 (duress) must be if the user is being forced to disarm (or arm) the...
  • Page 87: Adding A Master, Manager, Or Operator Code

    Section 9 – User Access Codes Adding a Master, Manager, or Operator Code Enter Installer Code † + [8] + new user no. (02-75) + During user code entry, normal key depressions at other keypads in a partition are new user’s code ignored.
  • Page 88: Changing A Master, Manager, Or Operator Code

    VISTA-50P/VISTA-50PUL Installation and Setup Guide Changing a Master, Manager, or Operator Code Enter Installer Code * + [8] + new user no. (02-75) + new user’s code * Or Master or Manager Code, but the code must be a higher level of authority than the code being changed (e.g. a Manager Code can add an Operator-level Code, but cannot add a Master or another Manager Code).
  • Page 89: Section 10: Testing The System

    • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Battery Test When AC power is present, the VISTA-50P/VISTA- If the VISTA-50P/VISTA-50PUL finds that the battery 50PUL runs a brief battery test every 60 seconds to voltage is low (less than approximately 11.5V), it...
  • Page 90: Testing Wireless Transmitters

    VISTA-50P/VISTA-50PUL Installation and Setup Guide Step Action Check the keypad-initiated alarms, if programmed, by pressing the panic key pairs (✳ and #, 1 and ✳, and/or 3 and #). The word ALARM and a descriptor “99” are displayed for ✳ and #. If [1] and [✳] are pressed, “95”...
  • Page 91: Trouble Conditions

    Section 10 – Testing The System Trouble Conditions Check Messages Power Failure Display Description Display Description CHECK AC LOSS This indicates that a problem exists on This indicates that the system is the zone number displayed. Zone trouble operating on battery power only. Check POWER may be caused by one of the following to see that the circuit breaker for the...
  • Page 92 • Note your customer number and/or company name. Technical Support:............ 1-800-645-7492 (8 a.m.-8 p.m. EST) ATLIS-FAX FAXBACK Automated Fax Retrieval System:....1-800-573-0153 or ....................1-516-921-6704 / ext. 1667 World Wide Web Address: .......... http:// www.honeywell.com/security 10-4 WWW.DIYALARMFORUM.COM...
  • Page 93: Appendix A: Regulatory Agency Statements

    The control cabinet must be protected from unauthorized access. This can be done by installing a tamper switch on the cabinet door (not supplied with VISTA-50P/VISTA-50PUL) or by installing a UL Listed passive infrared detector positioned to detect cabinet access. Wire the selected device to any EOLR-supervised zone (Zone 1-8). Program this zone for day trouble/night alarm (type 05) or 24-hour audible alarm (type 07) response.
  • Page 94: Ul611/Ul1610 Central Station Burglary Alarm

    • Also connect the 7720’s radio fault output to one of the VISTA-50P/VISTA-50PUL’ EOLR-supervised zones (i.e., 1-8). Program this zone for a trouble by day/alarm by night (type 05) or a 24-hour alarm (type 07, 08) response to radio faults.
  • Page 95 Appendix A – Regulatory Agency Statements FEDERAL COMMUNICATIONS COMMISSION (FCC) PART 15 STATEMENT NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation.
  • Page 96 VISTA-50P/VISTA-50PUL Installation and Setup Guide CANADIAN EMISSIONS STATEMENTS This Class B digital apparatus complies with Canadian ICES-003 NOTICE AVIS L’étiquette d’Industrie Canada identifie The Industry Canada Label identifies certified matériel homologué. Cette étiquette certifie que le equipment. This certification means that the matériel est conforme aux normes de protection,...
  • Page 97: Appendix B: Summary Of System Commands

    A P P E N D I X Summary of System Commands • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • User Code Add A User Code = User Code + 8 + New User Number + New User’s Code Commands...
  • Page 98 VISTA-50P/VISTA-50PUL Installation and Setup Guide WWW.DIYALARMFORUM.COM...
  • Page 99: Appendix C: Specifications

    • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • VISTA-50P/VISTA-50PUL CONTROL Physical: Standard Cabinet (included) 12 1/2"...
  • Page 100 VISTA-50P/VISTA-50PUL Installation and Setup Guide WWW.DIYALARMFORUM.COM...
  • Page 101: Appendix D: Contact Id Event Codes

    A P P E N D I X Contact ID Event Codes • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • TABLE OF CONTACT ID EVENT CODES Code Definition...
  • Page 102 VISTA-50P/VISTA-50PUL Installation and Setup Guide WWW.DIYALARMFORUM.COM...
  • Page 103: Index

    Index • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • #93 Menu Mode Programming ........
  • Page 104 VISTA-50P/VISTA-50PUL Installation and Setup Guide Call Waiting Defeat............ 5-12 Downloading Requirements .........7-1 Callback............... 7-2 Dual Reporting .............5-5 Callback Requested ............ 7-1 Duress Codes Level 6 ..........9-2 CANADIAN EMISSIONS STATEMENTS ....A-4 Duress Reporting ............9-2 Changing a User Code..........9-4 Check Messages ............10-3 Checksum Verification..........
  • Page 105 Ground Start Module ..........3-18 Manager Codes Level 2 ..........9-1 Master Codes Level 1 ..........9-1 Master Keypad .............2-3 Hardwire and Optional Expansion Zones ....1-1 MODEM COMM ..........7-1, 10-3 Hardwired (HW) Type 01..........4-6 modems................7-1 Holiday Schedule ............6-3 Mounting the Control Cabinet ........3-1 Holiday Schedule Programming ........
  • Page 106 VISTA-50P/VISTA-50PUL Installation and Setup Guide Primary Format............5-5 RJ31X ................3-6 Primary Phone Number ..........5-4 RJ31X jack ..............3-21 Primary Subscriber’s Account Number......5-3 RLY VOICE DESCR.............4-3 Printer Baud Rate............5-13 Printer Configurations..........3-20 Program Modes ............4-1 Programming............... 4-1 Scheduling ............1-2, 6-1 Programming Commands..........
  • Page 107 Time Driven Events ............. 6-2 VIP Module..............3-20 Time Driven Events Worksheet ........6-7 VIP Module Phone Code..........5-2 Time Window Definitions..........6-2 VISTA-50P/VISTA-50PUL Current Load....3-27 Time Windows............6-4, 6-5 Time Windows Programming ........6-5 Timed Events .............. 6-5 Time-Driven Event Programming ........ 6-8 Wheelock AS-121575W ..........3-4...
  • Page 108: The Limitations Of This Alarm System

    WARNING! THE LIMITATIONS OF THIS ALARM SYSTEM While this System is an advanced wireless security system, it does not offer guaranteed protection against burglary, fire or other emergency. Any alarm system, whether commercial or residential, is subject to compromise or failure to warn for a vari- ety of reasons.
  • Page 109: Limited Warranty

    LIMITED WARRANTY Honeywell International Inc., 165 Eileen Way, Syosset, New York 11791, warrants its product(s) to be in conformance with its own plans and specifications and to be free from defects in materials and workmanship under normal use and service for 24 months from the date stamp control on the product(s) or, for product(s) not having a date stamp, for 12 months from date of original purchase unless the installation instructions or catalog sets forth a shorter period, in which case the shorter period shall apply.
  • Page 110 WWW.DIYALARMFORUM.COM...
  • Page 111 WWW.DIYALARMFORUM.COM...
  • Page 112 165 Eileen Way, Syosset, New York 11791 Copyright © 2004 Honeywell International, Inc. www.honeywell.com/security ¬19(l WWW.DIYALARMFORUM.COM N5944-6V2 5/04 Rev A...

This manual is also suitable for:

Vista-50pul

Table of Contents