Low Voltage Directive; Installation - YOKOGAWA DPharp EJX110A User Manual

Differential pressure and pressure transmitters
Hide thumbs Also See for DPharp EJX110A:
Table of Contents

Advertisement

• EJX110A-MS, EJX110A-HS,
EJX110A-VS, EJX130A, EJX440A,
EJX510A-D, and EJX530A-D can be used
above 200 bar and therefore considered as
a part of a pressure retaining vessel where
category III, Module H applies. These models
with option code /PE3 conform to that category.
(2) Technical Data
• Models without /PE3
Article 3, Paragraph 3 of PED, denoted as
Sound Engineering Practice (SEP).
• Models with /PE3
Module: H
Type of Equipment: Pressure Accessory-Vessel
Type of fluid: Liquid and Gas
Group of fluid: 1 and 2
1
Capsule
PS*
Model
code
(bar)
L
160
EJX110A
M, H, V
250
EJX110A
with code
M, H, V
250
/PE3
EJX130A
M, H
500
EJX130A
with code
M, H
500
/PE3
EJX310A L, M, A, B
160
EJX430A
H, A, B
160
EJX440A
C, D
500
EJX440A
with code
C, D
500
/PE3
A, B, C
100
EJX510A
D
700
EJX510A
with code
D
700
/PE3
A, B, C
100
EJX530A
D
700
EJX530A
with code
D
700
/PE3
*1:
PS is maximum pressure for vessel itself based on
Pressure Equipment Directive 97/23/EC. Refer to
General Specification for maximum working pressure of a
transmitter.
*2:
Referred to Table 1 covered by ANNEX II of EC Directive
on Pressure Equipment Directive 97/23/EC
PS.V
2
V(L)
Category*
(bar.L)
Article 3,
0.01
1.6
Paragraph 3
0.01
2.5
(SEP)
0.01
2.5
III
Article 3,
0.01
5.0
Paragraph 3
(SEP)
0.01
5.0
III
Article 3,
0.01
1.6
Paragraph 3
(SEP)
Article 3,
0.01
1.6
Paragraph 3
(SEP)
Article 3,
0.1
5.0
Paragraph 3
(SEP)
0.1
5.0
III
Article 3,
0.1
10
Paragraph 3
0.1
70
(SEP)
0.1
70
III
Article 3,
0.1
10
Paragraph 3
0.1
70
(SEP)
0.1
70
III
<2. Handling Cautions>
(3) Operation
CAUTION
• The temperature and pressure of fluid should
be maintained at levels that are consistent
with normal operating conditions.
• The ambient temperature should be
maintained at a level that is consistent with
normal operating conditions.
• Please take care to prevent water hammer
and the like from inducing excessive
pressures in pipes and valves. If phenomena
are likely, install a safety valve or take
some other appropriate measure to prevent
pressure from exceeding PS.
• Take appropriate measures at the device or
system level to protect transmitters if they
are to be operated near an external heat
source.

2.12 Low Voltage Directive

Applicable standard: EN61010-1
(1) Pollution Degree 2
"Pollution degree" describes the degree to
which a solid, liquid, or gas which deteriorates
dielectric strength or surface resistivity is
adhering. " 2 " applies to normal indoor
atmosphere. Normally, only non-conductive
pollution occurs. Occasionally, however,
temporary conductivity caused by condensation
must be expected.
(2) Installation Category I
"Overvoltage category (Installation category)"
describes a number which defines a transient
overvoltage condition. It implies the regulation
for impulse withstand voltage. " I " applies to
electrical equipment which is supplied from the
circuit when appropriate transient overvoltage
control means (interfaces) are provided.
2-12
IM 01C25B01-01E