Protection Controls; Pressure Protection Control - LG MULTI V ARUN072BTE4 Service Manual

Heat pump and heat recovery variable refrigerant flow outdoor units 6.0 to 42.0 tons
Hide thumbs Also See for MULTI V ARUN072BTE4:
Table of Contents

Advertisement

PROTECTION CONTROLS

Pressure Protection Control

Pressure Protection Control
Pressure Control in Cooling Mode
Table 12: High Pressure Control in Cooling Mode.
Pressure Range
Pd ≥ 580 psi
548 psi
519 psi
Pd > 548 psi
Pd ≥ 510 psi
Pd ≥ 505 psi
Pd < 505 psi
* Frequency Hold = Frequency (or RPM) is not increasing (can decrease).
Table 13: Low Pressure Control in Cooling Mode.
Pressure Range
Ps ≤ 14 psi, One (1) minute After Operation
Ps ≤ 118 psi, One (1) minute Before Operation
Pressure Control in Heating Mode
Table 14: High Pressure Control in Heating Mode.
Pressure Range
Pd ≥ 581 psi
Pd > 495 psi
Table 15: Low Pressure Control in Heating Mode.
Pressure Range
Ps ≤ 14 psi
Ps ≤ 18 psi
Ps ≤ 20 psi
Ps ≤ 28 psi
Ps ≥ 28 psi
* Frequency Hold = Frequency (or RPM) is not increasing (can decrease).
14
Compressor
-15 Hz / 10 seconds
Frequency Hold*
+2 Hz or less / 10 seconds
Compressor
-15Hz / 10 seconds
Compressor
-15 Hz / 10 seconds
Compressor
-15 Hz / 10 seconds
Frequency Hold*
+2 Hz or less / 10 seconds
Normal Control
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Stop
Normal Control
Stop
Stop
Stop
Fan
Stop
+100 RPM / 10 seconds
+100 RPM / 10 seconds
+100 RPM / 10 seconds
Fan
Stop
-100 RPM / 10 seconds
Fan
Stop
-50 RPM / 10 seconds
Fan
Stop
+100 RPM / 10 seconds
+100 RPM / 10 seconds
+100 RPM / 10 seconds
Normal Control